SECTION II
Installation
Page 2.6
BP+10-150
12/95
2.4 Signal Wiring (continued)
2.4.1 Remote Control
(TB1)
(continued)
b.
Battery Trip and Position
1.
24 Vdc UVR control for battery disconnect, 0.6 amp max.
2.
Contact indicates position of battery disconnect.
c.
Remote On-Generator Condition
—
Isolated contact closure signals
UPS logic that a generator is supplying UPS input power.
d.
Summary Alarm (NO/NC)
1.
120 Vac—0.5 amps ac max.
2.
28 Vdc
—
1 amp ac max.
Terminal wire sizing : #22-#12 AWG
2.4.2 Optional Remote Status Panel (TB2)
Ten position terminal for direct connection between UPS and TB1 in the
Remote Status Panel. Terminal wire size #22-#14 AWG (recommended: #16 AWG).
2.4.3 Optional RS232 Communication (J6-J9)
25 Pin D-Sub Receptacles (male), DTE and DCE are provided for COM Ports
1 and 2. Communication shall be selectable from either standard ANSI
terminal format or P-Record protocol.
2.4.4 Optional Modem Connection (J1O-J13)
Two modem port line and two modem port phone connections are included.
Accepts standard RJ11 plugs. Communication shall be selectable from either
standard ANSI terminal format or P-Record protocol.