SECTION II
Installation
Page 2.8
BP+10-150
12/95
2.6 Connecting the Cabinets
1. If Battery Cabinet #1 is to be attached
to the left side of the UPS, fasten the two
cabinets together using the four (4) 5/16” x 1”
bolts, nuts and washers packed with the
leveling feet (see Figure 2-2).
2. If two or more battery cabinets are to
be installed, remove the left-hand fiberboard
shipping panel of the first cabinet and the right-
hand cover of the second cabinet in the same
way. Plug the power and signal wire electrical
connectors together. Bolt the two cabinets
together as described. Repeat for any additional
battery packs.
2.7 Re-assembly
1. Replace side cover(s) of battery cabinets, attaching screws on inside
(removed in Paragraph 2.3, Step 3).
Be very careful not to touch screwdriver
against the battery terminals.
2. Replace the clear plastic guard and metal cover on the front of the UPS
(removed in Paragraph 2.2, Step 6a).
3. The complete assembly, UPS and battery cabinet(s), can now be rolled on
its casters back to eliminate the work area behind it. When it is in its final location,
lower the leveling feet to stabilize and level the cabinets. Tighten locking nuts.
NOTE: For proper maintenance access and ventilation, a clear area three
feet (91 cm) in front of the UPS and one foot (30.5 cm) above it is recommended.