Troubleshooting 30
7.11 P6(Low Pressure Protection Diagnosis and Solution)
Description:
If the sampling voltage is not 5V, the LED displays a failure code.
Recommended parts to prepare:
• Connection wires
• Low pressure protector
• Indoor fan assembly
• Outdoor PCB
Troubleshooting and repair:
Low pressure protection
Low pressure protection
Are the low pressure protector
and main control board wired
properly?
Are the low pressure protector
and main control board wired
properly?
Yes
Reconnect the low pressure protector
and main control board
Reconnect the low pressure protector
and main control board
Replace outdoor main board
Replace outdoor main board
No
Replace low pressure protector
Replace low pressure protector
Is the outdoor ambient
temperature too low?
Is the outdoor ambient
temperature too low?
No
Stop the unit
Stop the unit
Yes
Open the valve core of the high
pressure valve
Open the valve core of the high
pressure valve
No
Is the valve core of the high
pressure valve fully opened?
Is the valve core of the high
pressure valve fully opened?
Is the indoor fan running
properly in cooling mode?
Is the indoor fan running
properly in cooling mode?
Refer to the solution to the malfunction
of fan speed being out of control. Find
the cause and resolve the problem.
Refer to the solution to the malfunction
of fan speed being out of control. Find
the cause and resolve the problem.
No
Yes
Yes
Check whether the refrigerant
system is functioning properly.
Check whether the refrigerant
system is functioning properly.
No
Is it in working order?
Is it in working order?
No
When the level of refrigerant is
not sufficient, doe the system
function properly after more
refrigerant is added?
When the level of refrigerant is
not sufficient, doe the system
function properly after more
refrigerant is added?
Is the low pressure protector
broken?Method: Disconnect the
plug. Measure the resistance of
the low pressure protector. If the
protector is normal the value is o.
Is the low pressure protector
broken?Method: Disconnect the
plug. Measure the resistance of
the low pressure protector. If the
protector is normal the value is o.
No
Yes
Содержание U6MRS32-18
Страница 1: ...SERVICE MANUAL ENGLISH AIR CONDITIONING SYSTEMS LCAC...
Страница 4: ......
Страница 5: ...Contents 1 Precautions 2 2 Information servicing For flammable materials 3 Safety Precautions...
Страница 11: ...Contents 1 Model Reference 2 2 External Appearance 3 Model Reference...
Страница 13: ...Model Reference 3 2 External Appearance 2 1 Indoor Unit Compact Four way Cassette A6 Duct Floor Ceiling...
Страница 14: ...Model Reference 4 2 2 Outdoor Unit Outdoor Unit...
Страница 18: ...IDU Compact Cassette 4 2 Dimensional Drawings...
Страница 20: ...IDU Compact Cassette 6 4 Service Place...
Страница 23: ...IDU Compact Cassette 9 Heating airflow velocity distributions Heating temperature distributions...
Страница 25: ...IDU Compact Cassette 11 Heating airflow velocity distributions Heating temperature distributions...
Страница 49: ...IDU A6 Duct 8 6 Fan Performance 18K...
Страница 50: ...IDU A6 Duct 9 Constant air volume...
Страница 67: ...IDU Floor Ceiling 4 3 Part names Air inlet Display panel Air outlet grille Louver Installation part...
Страница 68: ...IDU Floor Ceiling 5 4 Service Place 35mm 1 38in 1m 3 28ft 35mm 1 38in 35mm 1 38ch...
Страница 93: ...Outdoor Unit 3 Panel Plate B30...
Страница 94: ...Outdoor Unit 4 Panel Plate BA30...
Страница 95: ...Outdoor Unit 5 Panel Plate CA30...
Страница 96: ...Outdoor Unit 6 Panel Plate D30...
Страница 97: ...Outdoor Unit 7 Panel Plate E30...
Страница 98: ...Outdoor Unit 8 Panel Plate 590...
Страница 99: ...Outdoor Unit 9 2 Service Place...
Страница 110: ...Wiring Diagrams Outdoor unit wiring diagram 16022000022493...
Страница 111: ...Outdoor unit printed circuit board diagram 17122000002718...
Страница 280: ...AIR CONDITIONING SYSTEMS LCAC Scan here to download the latest version of this manual...