Product Features
9
3.5.3 Outdoor Fan Control:
Case 1:
• The outdoor unit will be run at different fan speed
according to T4 and compressor frequency.
• For different outdoor units, the fan speeds are
different.
Case 2:
• The outdoor unit will be run at different fan speed
according to T4.
• For different outdoor units, the fan speeds are
different.
3.5.4 Defrosting mode
Case 1:
• The unit enters defrosting mode according to the
temperature value of T3 and T4 as well as the
compressor running time.
• In defrosting mode, the compressor continues to run,
the indoor and outdoor motor will cease operation,
the defrost light of the indoor unit will turn on, and
the “
” symbol is displayed.
• If any one of the following conditions is satisfied,
defrosting ends and the machine switches to normal
heating mode:
• T3 rises above TCDE1.
• T3 maintained above TCDE2 for 80 seconds.
• Unit runs for 15 minutes consecutively in defrosting
mode.
Case 2:
• The unit enters defrosting mode according to the
temperature value of T3 as well as the compressor
running time.
• In defrosting mode, the compressor continues to run,
the indoor and outdoor motor will cease operation,
the defrost light of the indoor unit will turn on, and
the “
” symbol is displayed.
• If any one of the following conditions is satisfied,
defrosting ends and the machine switches to normal
heating mode:
• T3 rises above TCDE1.
• T3 maintained above TCDE2 for 80 seconds.
• Unit runs for 10 minutes consecutively in defrosting
mode.
•
3.5.5 Evaporator Coil Temperature Protection
• When the evaporator temperature exceeds a preset
protection value, the compressor ceases operation.
3.6 Auto-mode
• This mode can be selected with the remote controller
and the temperature setting can be adjusted between
16°C~30°C.
• In auto mode, the machine selects cooling, heating, or
fan-only mode on the basis of
∆
T (
∆
T =T1-TS).
∆
T
Running mode
∆
T>2
°C(
3.6
°F)
Cooling
-3
℃
(
-5.4
°F)
≤∆
T
≤
2
°C(
3.6
°F) Fan-only
∆
T<-3
°C(
-5.4
°F)
Heating*
Heating*: In auto mode, cooling only models run the fan
• Indoor fan will run at auto fan speed.
• The louver operates same as in relevant mode.
• If the machine switches mode between heating and
cooling, the compressor will keep stopping for certain
time and then choose mode according to
∆
T.
3.7 Drying mode
• In drying mode, AC operates the same as auto fan in
cooling mode.
• All protections are activated and operate the same as
they do that in cooling mode.
• Low Room Temperature Protection
If the room temperature is lower than 10°C, the
compressor ceases operations and does not resume until
room temperature exceeds 12°C.
3.8 Forced operation function
Press the AUTO/COOL button, the AC will run as below
sequence:
Forced auto
→
Forced cooling
→
Off
• Forced cooling mode:
The compressor and outdoor fan continue to run and
the indoor fan runs at breeze speed. After running for 30
minutes, the AC will switch to auto mode with a preset
temperature of 24°C(76°F).
• Forced auto mode:
Forced auto mode operates the same as normal auto mode
with a preset temperature of 24°C(76°F).
• The unit exits forced operation when it receives the
following signals:
Содержание U6MRS32-18
Страница 1: ...SERVICE MANUAL ENGLISH AIR CONDITIONING SYSTEMS LCAC...
Страница 4: ......
Страница 5: ...Contents 1 Precautions 2 2 Information servicing For flammable materials 3 Safety Precautions...
Страница 11: ...Contents 1 Model Reference 2 2 External Appearance 3 Model Reference...
Страница 13: ...Model Reference 3 2 External Appearance 2 1 Indoor Unit Compact Four way Cassette A6 Duct Floor Ceiling...
Страница 14: ...Model Reference 4 2 2 Outdoor Unit Outdoor Unit...
Страница 18: ...IDU Compact Cassette 4 2 Dimensional Drawings...
Страница 20: ...IDU Compact Cassette 6 4 Service Place...
Страница 23: ...IDU Compact Cassette 9 Heating airflow velocity distributions Heating temperature distributions...
Страница 25: ...IDU Compact Cassette 11 Heating airflow velocity distributions Heating temperature distributions...
Страница 49: ...IDU A6 Duct 8 6 Fan Performance 18K...
Страница 50: ...IDU A6 Duct 9 Constant air volume...
Страница 67: ...IDU Floor Ceiling 4 3 Part names Air inlet Display panel Air outlet grille Louver Installation part...
Страница 68: ...IDU Floor Ceiling 5 4 Service Place 35mm 1 38in 1m 3 28ft 35mm 1 38in 35mm 1 38ch...
Страница 93: ...Outdoor Unit 3 Panel Plate B30...
Страница 94: ...Outdoor Unit 4 Panel Plate BA30...
Страница 95: ...Outdoor Unit 5 Panel Plate CA30...
Страница 96: ...Outdoor Unit 6 Panel Plate D30...
Страница 97: ...Outdoor Unit 7 Panel Plate E30...
Страница 98: ...Outdoor Unit 8 Panel Plate 590...
Страница 99: ...Outdoor Unit 9 2 Service Place...
Страница 110: ...Wiring Diagrams Outdoor unit wiring diagram 16022000022493...
Страница 111: ...Outdoor unit printed circuit board diagram 17122000002718...
Страница 280: ...AIR CONDITIONING SYSTEMS LCAC Scan here to download the latest version of this manual...