iN401 - iN501 Adjusting
CO2
Level
34
May
2019
-
Revision
00
12. Press LOW FIRE on the display screen.
13. Record “initial output” in Low Fire Recorded Values table.
CO
2
and CO Standards
Description
CO
2
Range
Max. CO Level
Natural Gas Low Fire
9.1% to 9.3%
< 60 ppm
Propane Low Fire
10.1% to 10.5%
< 60 ppm
Low Fire Recorded Values
Date ____ / ____ / _______
Heat Engine
(TOP)
Initial Output
Adjusted Value
CO
2
Value %
Max CO ppm
Heat Engine
(BOTTOM)
Initial Output
Adjusted Value
CO
2
Value %
Max CO ppm
14. Adjust the Low Fire screw while the burner operates at
low fire using a 2mm hex wrench. Turn clockwise to
increase CO
2
and counterclockwise to decrease CO
2
.
Low Fire Screw
15. Once the desired values are achieved, record the new
Low Fire CO
2
“adjusted values” in the table.
16. From the display screen, press Bottom Heat Engine and
repeat the Low Fire procedure for all heat engines.
17. When all heat engines have been properly adjusted, turn
off water flow.
18. Remove the flue gas analyzer probe and plug the test
port.
19. Press the back button to return to the main screen.
20. Check for gas leaks using a leak detector.
21. Install side panel covers. If converting to propane,
proceed to section “11. Natural Gas to Propane
Conversion” on page 35.
Содержание iN401
Страница 4: ......
Страница 44: ...iN401 iN501 Operation 40 May 2019 Revision 00 12 5 2 Changing Passcode ...
Страница 76: ...iN401 iN501 Product Warranty 72 May 2019 Revision 00 This page has been intentionally left blank ...
Страница 77: ...iN401 iN501 May 2019 Revision 00 NOTES ...
Страница 78: ...iN401 iN501 74 May 2019 Revision 00 NOTES ...
Страница 79: ...Endless water Zero waste ...