iN401 - iN501 Water
Connections
30
May
2019
-
Revision
00
8.4.1 Installing iB3001 to Condensate Drain Line
1. Install the unit so the inlet and outlet connections are
below the level of the condensate drain coming from the
gas-fired appliance.
a. A one inch minimum distance is required.
b. In the case of a floor mounted gas-fired appliance a
riser may be required to raise the gas-fired appliance
to obtain the minimum requirement.
2. Place the unit only in a horizontal position on the floor.
Vertical mounting is not permitted and will void the
warranty.
3. Any condensate drain connection must have a p-trap
between the gas-fired appliance outlet and the unit’s inlet.
4. Locate the unit where pipes are not subjected to freezing
temperatures.
5. Locate the unit close to a floor drain or use a condensate
pump.
6. Ensure that all connections are watertight.
7. Follow all local codes for handling exhaust gas
condensate.
8. Locate the unit near an electrical outlet.