Charge Amps
Amps.
This is the constant current charge amps for main
charge.
Max Charge Time Hours and
Minutes
If this value is set to a non zero value the charge will
stop or switch to the TopUp charge if one has been
set, at the preset time if the target voltage has not
been met.
Target Fail Time
Hours and
Minutes.
If a Max Charge Time has not been set the charge will
stop if this time is met before the target voltage has
been achieved. It will not switch to TopUp charge.
TopUp Amps.
Amps.
If a TopUp charge is required this is the constant
current TopUp current. If no TopUp is required set to
zero.
TopUp Time
Hours and
Minutes
If a TopUp charge is required this is the length of the
TopUp.
Cell Voltage Fall
Volts.
Cell Overcharge
Volts.
During the charge the cell voltage is detected and
stopped if the Overcharge Voltage is exceeded.
Cell Print Interval Minutes.
During the whole charge the cell voltages can be
printed at periodic intervals in minutes. If not required
set to zero. Note during the charge the cell voltages
can be manually printed at any time by pressing the '.'
key.