18. In the same manner, attach the other rail assembly to the other side.
19. Slide the middle rail toward the front until the rear bracket area is accessible.
20. Attach the rear end of the outer rail to the rear bracket with at least one screw. If
possible, attach at two places.
21. In the same manner, attach the other rail assembly to the other side.
22. Fully extend the left and right rails until the extension locks have engaged and the
rails will not push back in. The rail system is now ready to receive the chassis.
Caution:
Lifting and placing the chassis in the rails is a two-person job. If needed, use an
appropriate lifting device.
23. With the chassis front facing you, lift the chassis and carefully insert the rails
attached to the chassis in the extended rails.
24. Slide the chassis toward the rear of the cabinet until the rails lock together.
25. Depress and hold down the finger tabs on both extension locks while sliding the
chassis toward the rear.
26. Slide the chassis all the way into the rack until the chassis handles are against the
front posts.
Basic Rail Rack Mount Removal
1. Disconnect all cables from the back of the system.
Note:
Remember to use the system LED to properly identify the system you are servicing.
2. Pull system from rack until brackets are fully extended.
3. Push in both clips on the brackets and slide the system forward until the inner rail
separates from the outer rail.
4. Remove and service the system.
Basic Rail Rack Mount Installation
1. Extend the inner rail until it locks.
2. Depress the spring safety lock to release the inner rail.
3. Remove the inner rail from the rail assembly.
4. Attach the outer rail slides to the rack posts using two #10-32 x 1/2 screws at the
front posts, and two #10-32 x 1/2 screws at the rear posts.
Note:
The rail flanges mount to the inside of each post.
5. Insert the inner rails over the server chassis sidewall studs.
6. Slide the inner rails toward the front of the server chassis.
7. Secure the inner rails with one #6-32 x 1/4 screw for each rail.
Содержание SR1600UR - Server System - 0 MB RAM
Страница 4: ...iv Intel Server System SR1600UR Service Guide...
Страница 6: ...vi Intel Server System SR1600UR Service Guide...
Страница 8: ...viii Intel Server System SR1600UR Service Guide...
Страница 14: ...xiv Intel Server System SR1600UR Service Guide...
Страница 18: ...xviii Intel Server System SR1600UR Service Guide...
Страница 58: ...40 Intel Server System SR1600UR Service Guide Figure 25 Installing the Server System Cover TP02196 A B...
Страница 122: ...104 Intel Server System SR1600UR Service Guide...
Страница 126: ...108 Intel Server System SR1600UR Service Guide...
Страница 132: ...114 Intel Server System SR1600UR Service Guide...
Страница 142: ...124 Intel Server System SR1600UR Service Guide...
Страница 166: ...148 Intel Server System SR1600UR Service Guide...
Страница 190: ...172 Intel Server System SR1600UR Service Guide...