Thermal Management Logic and Thermal Monitor Feature
Thermal and Mechanical Design Guidelines
39
The processor uses the Digital Thermal Sensor (DTS) as the on-die sensor to use for
fan speed control (FSC). The DTS is monitoring the same sensor that activates the
TCC (see Section
4.2.2). Readings from the DTS are relative to the activation of the
TCC. The DTS value where TCC activation occurs is 0 (zero).
A T
CONTROL
value will be provided for use with DTS. The usage model for T
CONTROL
with
the DTS as below:
If the Digital thermal sensor reading is less than T
CONTROL,
the fan speed can be
reduced.
If the Digital thermal sensor reading is greater than or equal to T
CONTROL,
then T
C
must be maintained at or below the Thermal Profile for the measured power
dissipation.
The DTS T
CONTROL
value is factory configured and is written into T
OFFSET
MSR, the BIOS
can read the T
OFFSET
MSR and provide this value to the fan speed control device.
Figure
4-3. T
CONTROL
for Digital Thermal Sensor
Note:
The processor has only DTS and no thermal diode. The T
CONTROL
in the MSR is relevant
only to the DTS.
4.2.11
Platform Environmental Control Interface (PECI)
The PECI interface is a proprietary single wire bus between the processor and the
chipset or other health monitoring device. At this time the digital thermal sensor is the
only data being transmitted. For an overview of the PECI interface see
PECI Feature
Set Overview.
For additional information on the PECI see the datasheet.
The PECI bus is available on pin G5 of the LGA 775 socket. Intel chipsets beginning
with the ICH8 have included PECI host controller. The PECI interface and the
Manageability Engine are key elements to the
Intel
®
Quiet System Technology (Intel
®
Содержание BX80570E8200 - Core 2 Duo 2.66 GHz Processor
Страница 10: ...10 Thermal and Mechanical Design Guidelines...
Страница 26: ...Processor Thermal Mechanical Information 26 Thermal and Mechanical Design Guidelines...
Страница 82: ...Heatsink Clip Load Metrology 82 Thermal and Mechanical Design Guidelines...
Страница 84: ...Thermal Interface Management 84 Thermal and Mechanical Design Guidelines...
Страница 108: ...Balanced Technology Extended BTX System Thermal Considerations 108 Thermal and Mechanical Design Guidelines...
Страница 110: ...Fan Performance for Reference Design 110 Thermal and Mechanical Design Guidelines...
Страница 122: ...Mechanical Drawings 122 Thermal and Mechanical Design Guidelines Figure 7 50 Reference Fastener Sheet 1...
Страница 123: ...Mechanical Drawings Thermal and Mechanical Design Guidelines 123 Figure 7 51 Reference Fastener Sheet 2...
Страница 124: ...Mechanical Drawings 124 Thermal and Mechanical Design Guidelines Figure 7 52 Reference Fastener Sheet 3...
Страница 125: ...Mechanical Drawings Thermal and Mechanical Design Guidelines 125 Figure 7 53 Reference Fastener Sheet 4...