Jumper setting 

Description 

         

0~5Vdc. 
Input impedance is >70kOhm. 
Raw reading is about 10000 at 5.0V (0.5V per count). 

       

0~10Vdc. 
Input impedance is >70kOhm. 
Raw reading is about 10000 at 10.0V (1mV per count). 

       

0~30mA (suitable for 4~20mA transducers). 
An internal 100 Ohm resistor connects the input terminal to Common. 
Raw reading is about 10000 at 30mA (3uA per count). 

       

Contact, Pulse or Resistive (0~50Ohm). 
An Internal 10K resistor will hold the input to 5V. 

This is the factory default setting.

 

To access the input jumper settings, open the 

ezeio

™ by removing the four black screws.

 

 

 
Read the eze User Manual pages 13 through to and including page 16, covering input connections. 
 
 
 

Getting started with configuration. 

 

Go to 

www.ezecontrol.com

 

 

 
 

 
 
 

 
 
 
 
 
 

Click on the ‘Configure’ tab 
And then the + by the Inputs: 

Now select which input you wish to configure. Select the 
‘Input type’ to match the configuration of the ‘Jumper’ 
setting in the table above. Always remember to select 
‘Save Changes’ after making a change. 
 

Important Note:

 The analogue inputs have a nominal 

calibration only (ex factory), and where accuracy is  
required, individual calibration of each channel is  
required. This is done with the use of an accurate signal 
calibrator. 

Section 1

 covers the 

ezeio

 Controller 4 local inputs, and 

Section 2 

covers adding the power of the 2400-A16, to  

expand the inputs up to 40, plus adding more outputs. 

Section 1 - 

ezeio

 Controller. 

 

Configuring the 

ezeio

 Controller local inputs. 

The 

ezeio

™ controller has four standard inputs. Each input may be configured individually in one of the four ways  

described here:   

4~20mA 

Resistance or 
Pulse input 

 Enter your Account number, Login and Password. 

Содержание ezeio-GSM

Страница 1: ...ezeio Controller and the 2400 A16 input expansion Important Supplementary Manual...

Страница 2: ...m Page 14 Section 3 Alarms Page 15 Using a data GSM 3G SIM in the ezeio GSM Controller Page 16 Product Liability This information describes our products It does not constitute guaranteed properties an...

Страница 3: ...transceiver Ethernet port 4 analogue inputs and Modbus RTU RS 485 Comms ezeio Controller Compatibility The Modbus RTU RS 485 port on the ezeio controller can be used to connect to Intech Micro Station...

Страница 4: ...m Click on the Configure tab And then the by the Inputs Now select which input you wish to configure Select the Input type to match the configuration of the Jumper setting in the table above Always re...

Страница 5: ...s example we want to read 10 If you wish this to actually read another value for example 100 then enter 100 Click on Use 2 Now go to the eze Configure page and click on Input type and select Custom as...

Страница 6: ...good accuracy at a particular point of the span then calibrate at that point instead of the full span point 7 For the best average accuracy calibrate the scale between 0 75 of span 8 Apply this proce...

Страница 7: ...es 1 More than one 2400 A16 can be added to a ezeio controller 2 The ezeio Controller will accept up to 40 inputs total per ezeio controller this also includes the 4 analogue inputs on the ezeio contr...

Страница 8: ...Software Click on the Auto Detect 2400 Station button Configure the required input channel settings as shown The 2 important areas to make the same as the eze is the Baud rate and the Port Settings Th...

Страница 9: ...ng address may be set to 2 Enter your Account number Login and Password The first task is to add the 2400 A16 onto the ezeio Controller Click on the Configure tab and wait for the Configure screen to...

Страница 10: ...ure input scaling for RTD s and thermocouples Select Custom for all 2400 A16 input configurations Type in these 2 calibration details for all listed temperature probes both RTD and Thermocouple The 24...

Страница 11: ...splays input values from the selected range Table of how eze scales this input 2400 A16 output value to eze eze Raw value 0 0 100 100 000 Select Custom Click on Linear analog Point 1 is the zero point...

Страница 12: ...m Click on Linear analog Point 1 is the zero point As the pressure transmitter range is 1 at minimum range the Raw value and the pressure sensor value 0 but the Value 1Bar Point 2 is Full Scale which...

Страница 13: ...sec Therefore 1250 will be value used for full scale reading The 2400 A16 calculates this Hz input the same as the normal analogue input 0Hz 0 and 100Hz 100 Select Custom Click on Linear analog Point...

Страница 14: ...puts on the 2400 A16 are also available but need to be initialised by eze On Site Calibration Trim When an onsite calibration offset or zero adjustment is required to correct the reading on the eze we...

Страница 15: ...2 Two set point settings are required one for setting the alarm and the 2nd for unsetting the alarm as per this screen shot 3 Example for configuration of a SMS text alarm message When in this alarm...

Страница 16: ...e Configuration area click on System Setting required for New Zealand GPRS APN leave all other areas blank match to your provider as listed below 7 Click Save changes Remove the Ethernet connection an...

Отзывы: