12
Click on ‘Save changes’.
Click on the ‘Status’ tab to see the flow meter reading.
Example 2.2:
This next example is a compound range such as a pressure transmitter that has a span of -1~9Bar.
Select ‘Custom’.
Click on ‘Linear analog’.
Point 1 is the zero point. As the pressure transmitter range is -1 at
minimum range, the Raw value and the pressure sensor value = 0, but
the Value = -1Bar.
Point 2 is Full Scale, which in this case is 9Bar. At full scale input, the
Raw value will be 100000, and the Value = 9.
Click on ‘Use’ to enter this calibration setting.
Click on ‘Save changes’.
Click on the ‘Status’ tab to see the pressure.