11
Click on ‘Save changes’.
Example 2:
For all other analogue values the 2400-A16 outputs to
eze
, 0~100% over the range selected on the
2400-A16 as per the table shown, which makes configuration very easy.
Click on the ‘Status’ tab to see the Temperature.
The
ezeio
controller displays input values from the selected range.
Table of how
eze
scales this input:
2400-A16 output
value to
eze
eze
Raw value
0 0
100 100,000
Select ‘Custom’.
Click on ‘Linear analog’.
Point 1 is the zero point. As the flow meter range is 0~60m3/Hr, at zero
flow, the Raw value and the flow meter value = 0.
Point 2 is Full Scale, which in this case is 60m3/Hr. At full scale input,
the Raw value will be 100000, and the flow meter value = 60.
Click on ‘Use’ to enter this calibration setting.