Intech Instruments ezeio-GSM Скачать руководство пользователя страница 16

 

16 

eze/2400-A16  250314 

www.intech.co.nz 

Christchurch Ph: +64 3 343 0646  

Auckland Ph: 09 827 1930  
Email: 

[email protected]

 

Using a data GSM/3G SIM in the 

eze

io-GSM Controller. 

 
This section is for the 

ezeio-GSM

 controller model only. 

1.  Obtain a data GSM/3G SIM with no password. (Note: the ezeio-GSM controller takes a standard size SIM card.) 
2.  Place SIM in a mobile phone to activate as per the providers instructions, or get the provider to do this at the time of 

purchase. 

3.  Place the SIM in the ezeio-GSM Controller with the chisel edge of the SIM at the top left (as shown circled below). 
4.  Follow the instructions in the ezeio-GSM Controller Instruction Manual starting page 21. 

 
 
 
 
 
 
 
 
 
 

5.  Connect via Ethernet and login to 

www.ezecontrol.com

 

6.  In the eze Configuration area, click on “System”: 

 
Setting required for New Zealand - 

GPRS APN 

(leave all other areas blank) - match to your provider as listed below: 

 
 
 
 
 
 
 
7.  Click ‘Save changes’. Remove the Ethernet connection and turn the Power off/on. Check that a connection via 

GSM/3G has been established in the eze System. 

 
 
If you are outside New Zealand please contact your local GSM/3G provider for the data GSM/3G SIM and the APN  
settings needed. 
 
 

Note: 

Initial connection via Ethernet is required for ezeio setup before the GSM/3G connection can be used. 

 
 
 
 

Important: 

We strongly recommend having the 

data GSM/3G SIM on account.

 

 

Using Prepay will result in no connection if the credit runs out 

(if this happens, then once more credit has been 

added, the eze system will need to have the power turned off/on in order to re-establish a connection).  
This is not an issue with on account data plans. 

Vodafone APN: 

vodafone

 

 
Telecom APN: 

wap.telecom.co.nz 

 
2degrees APN: 

internet

 

Содержание ezeio-GSM

Страница 1: ...ezeio Controller and the 2400 A16 input expansion Important Supplementary Manual...

Страница 2: ...m Page 14 Section 3 Alarms Page 15 Using a data GSM 3G SIM in the ezeio GSM Controller Page 16 Product Liability This information describes our products It does not constitute guaranteed properties an...

Страница 3: ...transceiver Ethernet port 4 analogue inputs and Modbus RTU RS 485 Comms ezeio Controller Compatibility The Modbus RTU RS 485 port on the ezeio controller can be used to connect to Intech Micro Station...

Страница 4: ...m Click on the Configure tab And then the by the Inputs Now select which input you wish to configure Select the Input type to match the configuration of the Jumper setting in the table above Always re...

Страница 5: ...s example we want to read 10 If you wish this to actually read another value for example 100 then enter 100 Click on Use 2 Now go to the eze Configure page and click on Input type and select Custom as...

Страница 6: ...good accuracy at a particular point of the span then calibrate at that point instead of the full span point 7 For the best average accuracy calibrate the scale between 0 75 of span 8 Apply this proce...

Страница 7: ...es 1 More than one 2400 A16 can be added to a ezeio controller 2 The ezeio Controller will accept up to 40 inputs total per ezeio controller this also includes the 4 analogue inputs on the ezeio contr...

Страница 8: ...Software Click on the Auto Detect 2400 Station button Configure the required input channel settings as shown The 2 important areas to make the same as the eze is the Baud rate and the Port Settings Th...

Страница 9: ...ng address may be set to 2 Enter your Account number Login and Password The first task is to add the 2400 A16 onto the ezeio Controller Click on the Configure tab and wait for the Configure screen to...

Страница 10: ...ure input scaling for RTD s and thermocouples Select Custom for all 2400 A16 input configurations Type in these 2 calibration details for all listed temperature probes both RTD and Thermocouple The 24...

Страница 11: ...splays input values from the selected range Table of how eze scales this input 2400 A16 output value to eze eze Raw value 0 0 100 100 000 Select Custom Click on Linear analog Point 1 is the zero point...

Страница 12: ...m Click on Linear analog Point 1 is the zero point As the pressure transmitter range is 1 at minimum range the Raw value and the pressure sensor value 0 but the Value 1Bar Point 2 is Full Scale which...

Страница 13: ...sec Therefore 1250 will be value used for full scale reading The 2400 A16 calculates this Hz input the same as the normal analogue input 0Hz 0 and 100Hz 100 Select Custom Click on Linear analog Point...

Страница 14: ...puts on the 2400 A16 are also available but need to be initialised by eze On Site Calibration Trim When an onsite calibration offset or zero adjustment is required to correct the reading on the eze we...

Страница 15: ...2 Two set point settings are required one for setting the alarm and the 2nd for unsetting the alarm as per this screen shot 3 Example for configuration of a SMS text alarm message When in this alarm...

Страница 16: ...e Configuration area click on System Setting required for New Zealand GPRS APN leave all other areas blank match to your provider as listed below 7 Click Save changes Remove the Ethernet connection an...

Отзывы: