DGC6 – UserManual
4.8.1 Service
Service of any kind must only be attempted with the system set to Service mode “on”. For calibration and service work
you first have to activate the special status mode on the controller. Only then you are allowed to change the safety
related parameters. The special operating mode is activated by, among others, the function Service ON.
Further parameters menu items are therefore only accessible in the Service ON state. The Service ON state is reset
to normal operation mode either automatically 15 minutes after the last key press or manually in the menu by the
operator.
Sensors can’t be switched into the “special mode” from the controller. It can only be done directly at the sensor using
the tool. Sensors in the “special mode” are not included in the alarm evaluation.
Symbol
Description
Default
Function
OFF
Service
OFF
OFF = No reading and changing of parameters.
ON = Controller in Special status mode,
parameters can be read and changed.