DGC6 – UserManual
4.8.6 Test Function of the Analog Outputs
This feature is only available in Special Mode.
With the test function you can enter the value (in mA) that should be physically output.
The test function via the controller can only be applied when the analog outputs are overridden (configuration 1 of
analog outputs in the system parameters of the associated device, see 4.8.4.8)
Analog Outputs
Test Function
Submenu 1
AO 1
Preset
4.02mA 0.00mA
Submenu 1
AO 1
Preset
12.00mA 12.00mA
AO 1
Preset
4.02mA 12.00mA
On the left, the current set point of the
AO is shown. On the right, there is the
pre-set value entered by the operator.
After confirming the AO accepts the
predetermined value and outputs it
physically. As the current set point is
transmitted again and again, the
confirmation appears in the display
at the left.