DGC6 – UserManual
Code
Gas Type
Formula
Meas. Range
1
Unit
2072
R401b
R401b
20-2000
ppm
2073
R402a
R402a
20-2000
ppm
2074
R402b
R402b
20-2000
ppm
2082
R403a
R403a
ppm
2078
R404a
R404a
20-300
ppm
2083
R407a
R407a
ppm
2080
R407c
R407c
20-300
ppm
2075
R408a
R408a
20-2000
ppm
2076
R409a
R409a
20-2000
ppm
2068
R410a
R410a
20-300
ppm
2067
R411a
R411a
20-300
ppm
2079
R416a
R416a
20-300
ppm
2084
R417a
R417a
20-2000
ppm
2081
R422d
R422d
20-300
ppm
2062
R434a
R434a
20-300
ppm
2069
R507
R507
20-2000
ppm
EXT
TempC
TempC
C
EXT
TempF
TempF
F
EXT
Humidity
Hum.
% RH
EXT
Pressure
Press
mbar
EXT
TOX
TOX
ppm
EXT
Comb.
Comb
% LEL
EXT
External
%
EXT
Digital3
%
1
Different measuring ranges are possible, but not listed here. For details see the sensor datasheets.
2
Oxygen measurements: Alarm at falling concentration
3
The use with the measuring range value: 1 results in a binary value output of the values 0 or 1.
4.8.3.4
Measuring Range Definition
The measurement range must be adapted to the working range of the connected gas sensor.
For additional control by the installer, the settings in the controller must mandatorily match with the used sensors. If
the types of gas and/or measurement ranges of the sensor don’t agree with the settings of the controller, the error
“EEPROM / configuration error” is generated, and the collective fault message is activated.
The range also affects the display of the measured values, alarm thresholds and hysteresis. For measuring ranges
<10 three decimals places, <100 two decimal places, <1000 one decimal place are displayed. For measuring ranges
=> 1000, the display is without decimal place. The resolution and accuracy of the calculation is not affected by the
different measuring ranges.