DGC6 – UserManual

 

Code

Gas Type

Formula

Meas. Range

1

Unit

3475

n-Pentane

C5H12

0-100

% LEL

3490

TOLUENE

C7H8

0-100

% LEL

3448

BUTYL ACETATE

C6H12O2

0-100

% LEL

3415

CYCLOHEXANE

C6H12

0-100

% LEL

3472

CYCLOPENTANE

C5H10

0-100

% LEL

3420

ETHANE

C2H6

0-100

% LEL

3465

ISOBUTANE

C4H10

0-100

% LEL

3476

ISOPENTANE

C5H12

0-100

% LEL

3402

LPG

LPG

0-100

% LEL

3496

Petrol Vapours

Petrol

0-100

% LEL

3497

Styrene

C8H8

0-100

% LEL

3493

Xylene

C8H10

0-100

% LEL

3495

Acetylene

C2H2

0-100

% LEL

C160

VOC

VOC

0-2000

ppm

2189

Ethylene

C2H4

0-1000

ppm

2125

Ammonia

NH3

0-3000

ppm

2053

Xylene

C8H10

0-300

ppm

D184

Sulphur hexafluoride

SF6

0-1000

ppm

1135

Bromine

Br2

0-2

ppm

1192

Nitrous oxide

N2O

0-2000

ppm

1183

Hydrogen cyanide

HCN

0-100

ppm

1185

Formaldehyde

CH2O

0-10

ppm

1188

Silane

SiH4

0-50

ppm

1189

Ethylene

C2H4

0-200

ppm

1190

Ozone

O3

0-200

ppm

1193

Chlorine

CL2

0-20

ppm

1196

Sulphur dioxide

SO2

0-100

ppm

1197

Hydrogen sulphide

H2S

0-200

ppm

1198

Fluorine

F2

0-2

ppm

1187

Phosphine

PH3

0-5

ppm

1194

Hydrogen

H2

0-1000

ppm

1181

Chlorine dioxide

ClO2

0-1

ppm

1147

Phosgene

COCl2

0-1

ppm

2066

R11

R11

ppm

2059

R12

R12

20-2000

ppm

2070

R22

R22

20-300

ppm

2061

R23

R23

20-2000

ppm

2060

R32

R32

ppm

2064

R123

R123

20-300

ppm

2077

R134a

R134a

20-300

ppm

2063

R1234yf

R1234yf

ppm

2065

R125

R125

ppm

2071

R401a

R401a

20-2000

ppm

Содержание MSR PolyGard 2 DGC6

Страница 1: ...Suite 100 Poway CA 92064 Ph 858 578 7887 888 GO INTEC inteccontrols com March 03 2020 Revision Digital Gas Controller Series PolyGard 2 DGC6 User Manual Software Controller from version 1 01 00 with...

Страница 2: ...s 10 4 2 Status Alarm 13 4 3 Status Relay 13 4 4 Menu Sensor Readings 13 4 5 Maintenance Information 15 4 6 Menu Data Logger 16 4 6 1 Data Logger Switch On Off 16 4 6 2 Current Values 16 4 6 3 CV Log...

Страница 3: ...33 4 8 3 8 Latching Mode Assigned to Alarm 33 4 8 3 9 SP Fault Assigned to Alarm 34 4 8 3 10 Alarm Assigned to Alarm Relay 34 4 8 3 11 SP Signal Assigned to Analog Output 34 4 8 4 Menu System Setup 35...

Страница 4: ...sensors with 4 to 20 mA signal interface are available in addition The controller can be employed as pure analog controller as analog digital or as digital controller The total number of connected se...

Страница 5: ...sensors need a running in period until the chemical process of the sensor reaches stable conditions During this running in period the sensor signal can create a false alarm Depending on the connected...

Страница 6: ...cursor position LED orange Flashes when alarm one or more alarms are active Permanently on when at least one relay is in manual mode LED red Flashes when alarm two and alarms of higher priority are ac...

Страница 7: ...a password level takes place when no buttons are pushed within 15 minutes The code levels are classified in order of priority Priority 1 has top priority Priority 1 Upper Level password 9001 not chang...

Страница 8: ...TEC 13 06 13 1 45am Display of gas concentration Power On Time Power On Time Main menu After 30 sec Starting menu or Controller information and general setup See from 4 7 Reading and change of the dat...

Страница 9: ...d in addition 4 1 1 Acknowledge a Fault According to the directives for gas measuring accumulated errors are allowed to be acknowledged automatically The automatic acknowledgment of a fault is only po...

Страница 10: ...ut 21 2 mA Cause Short circuit at analog input analog sensor not calibrated or defective Solution Check cable to analog sensor make calibration replace sensor AP Underrange Current signal at analog in...

Страница 11: ...ge of the processor Solution Replace device DP 0x EE Error 0x8010 Monitoring of the data storage reports an error Cause Electrical damage of the memory or configuration error Solution Check configurat...

Страница 12: ...odule Cause Bus line interrupted or short circuit EP_06 0X registered at the controller but not addressed or addressed incorrectly EP_06 0X module defective Solution Check line to EP_06 0X check modul...

Страница 13: ...Point No Digital measuring point X 1 96 where an alarm is pending S1 S1 Alarm status S1 Local alarm 1 active generated in the sensor module S1 Alarm 1 active generated in the central control 4 3 Stat...

Страница 14: ...32 CO Gas type See 4 7 3 ppm Gas unit See 4 7 3 A Average value Arithmetic average 30 measured values within the time unit C Current value Current value of gas concentration S Alarm SP has triggered a...

Страница 15: ...ctive relays in the menu Relay Parameters In this way one or more relays can be activated in case of maintenance see 4 8 2 9 In case of a pending maintenance message the phone no of the service compan...

Страница 16: ...urned off ON Data Logger function is turned on Note This function only works with an USB device If this function is active the USB device mustn t be removed otherwise data may be lost Like with Window...

Страница 17: ...5 29 09_50_09 0 20 20 28 0 25 29 09_50_10 0 20 20 28 0 25 29 09_50_11 0 20 20 28 0 25 29 09_50_12 0 20 20 28 0 0 29 The first column gives the time from the second column on the current values of all...

Страница 18: ...ws AEMMTT csv with MM standing for the current month and TT standing for the current day Every day a new file with the current date is generated This makes sure that the files won t be too big to be s...

Страница 19: ...nt Error date month day Time hours minutes Error text 10_22_28 DP 79 0x8100 03_30 10_20 Underrange 13_48_28 DP 79 0x8100 03_30 13_46 Underrange The first column gives the current time the second one t...

Страница 20: ...Language USA English Service Phone 888 464 6832 Time System US Time hh mm ss pm Date MM DD YY Error Delay 120s X Bus Slave Adr 1 MODBUS Display Parameter Main menu Submenu See 4 7 1 no intervention po...

Страница 21: ...in EU format hh mm ss Time hh mm ss pm hh mm ss pm Input of the correct time US format hh mm ss Input of the correct time EU format MM DD YY Date MM DD YY MM DD YY Input of the correct date US format...

Страница 22: ...can find the parameter functions of the gas controller Service OFF Parameters Main menu Submenu 1 See 4 8 1 password proTECted You can activate the following parameters only with Service ON Alarm Rel...

Страница 23: ...e special operating mode is activated by among others the function Service ON Further parameters menu items are therefore only accessible in the Service ON state The Service ON state is reset to norma...

Страница 24: ...rs Signal Relay 1 Not Used Selection of signal relay 1 96 Submenu 3 Relay Mode Used Relay Mode Energized Steady Flashing ON Alarm quantity 1 Time Recurr DI 0s Yes 0 External Mode DI 0 DI 0 Delay ON Ti...

Страница 25: ...ashing represents a connection option for warning devices to improve visibility If Flashing is set this mustn t be used as a safe output circuit A combination of relay mode energized with flashing ope...

Страница 26: ...ggered the horn will remain active until a reset action is performed After acknowledgment of the horn relay s clicking a button or via external DI input a timer starts When this time has expired and t...

Страница 27: ...point because the SPs can be assigned to each alarm separately in the menu SP Parameters This exception is used to build up targeted zone related signaling in case of SP errors which should not affec...

Страница 28: ...analog measuring point 1 32 Submenu 3 SP Mode not active Temporary Mode unlocked locked Nom Gas Unit 1110 CO ppm Measuring Range 250 ppm Stage Setpoint 1 C 25 ppm Stage Setpoint 2 C 50 ppm Stage Setp...

Страница 29: ...ssage at this measurement point Existing alarms and faults are cleared with deactivation Deactivated sensors do not output a collective fault message Symbol Description Default Function active SP Mode...

Страница 30: ...l D110 Carbon monoxide CO 0 2000 ppm 1130 Nitrogen dioxide NO2 0 30 ppm 1129 Nitrogen monoxide NO 0 100 ppm 1195 Oxygen O2 0 25 Vol 1125 Ammonia NH3 0 300 ppm D164 Carbon dioxide CO2 0 2000 ppm S164 C...

Страница 31: ...0 LEL C160 VOC VOC 0 2000 ppm 2189 Ethylene C2H4 0 1000 ppm 2125 Ammonia NH3 0 3000 ppm 2053 Xylene C8H10 0 300 ppm D184 Sulphur hexafluoride SF6 0 1000 ppm 1135 Bromine Br2 0 2 ppm 1192 Nitrous oxide...

Страница 32: ...measuring ranges are possible but not listed here For details see the sensor datasheets 2 Oxygen measurements Alarm at falling concentration 3 The use with the measuring range value 1 results in a bi...

Страница 33: ...2 Alarm 2 Gas concentration Threshold 3 Alarm 3 Gas concentration Threshold 4 Alarm 4 Gas concentration Threshold X Hysteresis Alarm X OFF Alarm release at increasing concentrations Alarm release at...

Страница 34: ...larm relays 1 32 4 8 3 11 SP Signal Assigned to Analog Output The measuring point signal current or average value can be assigned to one of the max 16 analog outputs The same assignment to different o...

Страница 35: ...No intervention possible See 4 8 4 1 No intervention possible See 4 8 4 1 Definition of the service interval See 4 8 4 2 Definition of average overlay See 4 8 4 3 Definition of average time See 4 8 4...

Страница 36: ...verlay 120 s 120 ppm sec Delay time of average value overlay ppm Threshold for average overlay 900 s AV Time 900 s sec Time for calculation of the average value Changes in the average time need a comp...

Страница 37: ...ule Symbol Description Default Function Analog Output 1 Selection of channel 0 Selection of the analog output 1 16 0 1 10 100 Selection of output signal 100 0 Analog output is not used therefore alway...

Страница 38: ...n off X Relay X should be multiplied information source 0 30 0 96 OUT AR Relay OUT SR Relay 0 0 Function off X Relay X target should switch together with IN relay Example 1 3 relay contacts are needed...

Страница 39: ...n over with Submenu 3 Relay 1 Test ON Relay 1 Test OFF Relay 1 Automatic Signal Relay 1 ON Signal Relay 1 OFF Signal Relay 1 Automatic The test function sets the target device selected relay in Specia...

Страница 40: ...he controller can only be applied when the analog outputs are overridden configuration 1 of analog outputs in the system parameters of the associated device see 4 8 4 8 Analog Outputs Test Function Su...

Страница 41: ...e equipotential bonding required also e g secondary potential to earth or grounding measures must be carried out in accordance with the respective project requirements It is important to ensure that n...

Отзывы: