DGC6 – UserManual
The controller monitors the communication between request and response. If the reply is too late, incomplete or
incorrect, the controller recognizes the following errors and reports them.
“SB 0X Error”
(0x9000) Communication error from central unit to SB 0X.
Cause:
Bus line interrupted or short circuit, DP 0X registered at the controller, but not
addressed. SB 0X defective.
Solution:
Check line to SB 0X, check SB address or SP parameters, replace sensor.
“DP 0X Error”
(0xB000) Communication error of SB to DP 0X sensor.
Cause:
Bus line between SB and head interrupted or short circuit, DP 0X registered at
the controller, but not configured at SB, wrong gas type, DP 0X defective.
Solution:
Check line to DP 0X, check sensor address or parameters, replace sensor.
“EP_06 0X Error”
(0x9000) Communication error to EP_06 0X module.
Cause:
Bus line interrupted or short circuit, EP_06 0X registered at the controller, but
not addressed or addressed incorrectly, EP_06 0X module defective.
Solution:
Check line to EP_06 0X, check module address, replace module.
“Maintenance”
(0x0080) System maintenance is due.
Cause:
Maintenance date exceeded.
Solution:
Perform the maintenance.
“DP XX locked”
“AP XX locked”
This SP input is locked (SP is physically present, but locked by the operator).
Cause:
Operator intervention.
Solution:
Eliminate the cause of a possible fault and then unlock the SP.
“UPS Error”
(0x8001) UPS doesn’t work correctly, can only be signaled by the GC.
Cause:
Defective UPS – too high or too low voltage.
Solution:
Replace UPS.
“Power Failure”
(0x8004) can only be signaled by the GC.
Cause:
Power failure or fuse tripped.
Solution:
Check power supply or fuses.
“Horn Error”
(0xA000) can only be signaled by the GC/EP with available hardware option.
Cause:
Wire break or device defective.
Solution:
??
“Warning Sign Error”
(0x9000) can only be signaled by the GC/EP with available hardware option.
Cause:
Wire break or device defective.
Solution:
??
“XXX FC: 0xXXXX”
Occurs, if there are several errors from one measuring point.
Cause:
Several causes.
Solution: