DGC6 – UserManual
3.3 Code Levels
According to the regulations of all national and international standards for gas warning systems, all inputs and changes
are protected by a four-digit numeric code (= password) against unauthorized intervention. The menu windows for
status messages and measuring values are visible without entering a code.
The cancellation of a password level takes place when no buttons are pushed within 15 minutes.
The code levels are classified in order of priority: Priority 1 has top priority.
Priority 1
: Upper Level (password 9001 – not changeable)
Code level priority 1 is intended for the service technician of the installer to change parameters and set-points. This
password allows working on all settings. For opening the parameter menus you must first activate the service mode
after code entry.
Priority 2
: Lower Level (password 1234 – not changeable)
Code level priority 2 allows the operator:
- to acknowledge faults
- to set date and time
- to configure and to operate the data logger option, after activation of the operation mode “Service Mode”
- to read all parameters
- to manually operate test