Installation and programming manual
Overview
7
[F] SmartLink Advanced telephone dialler
INIM's SmartLink/G and SmartLink/GP telephone dialers monitor the analogue landline and, in the event of
landline problems (line cutting, etc.) divert incoming and outgoing calls to the GSM network. The
SmartLink/P model operates solely over the PSTN line (landline).
[G] SmartLAN/485 Ethernet connection board (accessory item)
Allows the control panel to connect to an Ethernet network for remote connection. So it is possible to
modify the configuration parameters (up-download programming data) and/or manage the system using
the SmartLook supervision software based on graphical maps.
1.2
Other parts of the system
Zone:
a group of points (detectors, etc.) connected to a detection line. The control panel provides an extra
terminal (I/O) for each zone. If the terminal (I/O) is configured as an input, the control panel will be able to
split the detection line of each zone. This feature can be used when zones require a detector line that is
separate from the call point line in order to ensure proper operation of one line in the event of fault on the
other.
Switching power supply
: this unit, starting from the mains power supply (230V
) it connects to,
supplies the board with a 24V (27.6V
) stabilized current capable of feeding the control panel and
recharging the batteries. The EN54-4 compliant power-supply module is housed below the motherboard.
the mains power supply (230V
) the primary power source of the system. Refer to
paragraph 4.2 -
Internal devices
.
Batteries:
the secondary power source of the system. The panel enclosure houses two lead batteries @
12V 17Ah (connected in series). The system monitors the battery status (efficiency and charge). In the
event of inefficient or low battery conditions, the system will signal battery fault. In the event of primary
power failure (230V
), the batteries will take over automatically. If the problem persists for a long period
thus causing the battery charge to drop below the minimum value required, they will be shutdown
automatically in order to avoid damage. Refer to
paragraph 6.16
.
Thermal probe:
an accessory tool, to be connected to the panel and attached to the battery pack. This
device monitors the temperature of the external battery pack and regulates the battery charge accordingly.
Refer to
paragraph 6.17
.
RS485 BUS:
4 wire BUS for the repeater connections. Cabling must done with 4 pole braided shielded
cable. Refer to
paragraph 6.8 - Connecting the RS485 BUS
.
Timer:
a logical entity (the panel provides 8 timers) for automatic time-management of preset intervals (2
intervals per day) on preset days of the week and specific dates. The timers can be used in equations to
manage predefined operations or activate outputs.
Equation:
a group of logical conditions defined by the installer. An equation comprises a series of
operators (AND, OR, +, etc.) and a series of operands (Points, Zones, Timers, etc.). An equation can be
associated with an output that will activate when the equation is satisfied.
Holidays:
a list of days defined during the system configuration session which are associated with the
control panel timers.
1.3
The SmartLine fire alarm panel models
The available models are:
• SmartLine020-2 - Conventional fire alarm control panel with 2 zones non expandable
• SmartLine020-4 - Conventional fire alarm control panel with 4 zones expandable to 20
• SmartLine036-4 - Conventional fire alarm control panel with 4 zones expandable to 36