30
Installation instructions
Conventional fire detection control panel
6.4.2 SmartLetUSee/LCD-Lite repeater (accessory item)
1. Remove the four frontplate screws and lift off the frontplate.
2. Pass the cables through the cable entry on the back of the repeater.
3. Prepare the wall for the four 8mm anchor screws (stop screws) which must be positioned in accordance
with the holes on the backplate of the metal enclosure of the repeater.
4. Using the 4 anchor screws, attach the backplate of the repeater securely to the wall.
6.5
Connecting the lines
6.5.1 Connecting the detection lines
Each control panel zone has a pair of detector or call point connection terminals (detection line).
Attention:
In order to validate the IMQ-SECURITY SYSTEMS, NOT more 512 detectors and/or manual
call points can be connected.
The following diagrams illustrate the detection line wiring of the IRIS devices from INIM (see Appendix A -
Iris devices
):
Figure 14 - Connecting Iris detectors
Figure 15 - Connecting Iris call points
If detectors and call points are wired as per the diagram and the zone "Monitor Call points" option is
enabled, the control panel will discriminate between detector and call point triggered alarms.
ORANGE
WHITE
RED
GOLD
ORANGE
WHITE
RED
GOLD