Installation and programming manual
Programming from panel
55
9.6
Setting up equations
From panel:
NOT available
This section (available form SmartLeague software only) will allow you to define 7 equations that the
control panel can use in order to activate the outputs.
Each equation can be defined using operands (zone signals, timers and constants) and operators (AND,
OR, NOT, XOR, + , >, >=, <, <=, !=, =).
Night silence time
The duration (0 to 10 minutes) of Silence status when the system is operating in Night
mode (starting from the moment the
SILENCE
key is pressed).
Time lock reset
The period (0 to 30 minutes), after extinction activation, when reset operations are not
allowed. If a confirm extinction signal is sent to the extinction module during this period,
reset operations will be re-enabled.
Time reset
Line reset time (2 to 10 seconds): during this period the power supply to the line is
removed, in order to restore the detectors to standby after an alarm.
Time ignore
During this period (1 to 5 seconds), which starts after reset, the lines will not be taken
into account thus allowing the line devices to stabilize and restore to standby.
24VR cond.
If this option is set as “NO”, the AUX-R output will always be active except during Reset
time when it will be off.
If this option is set as “YES”, the AUX-R output will always be active except when one or
more of the zones listed under the option is set as “YES” go into alarm status.
Events on disabled
If enabled, this option allows the control panel to register in the log any change of status
of the disabled zones.
Slave on485
When activated, the control panel is seen as a power station connected to the SmartLoop
RS485 bus in slave mode.
After this option is activated it is possible to change the address of the control panel:
From panel:
<key>, Programming, Configuration, Acquire int.bus, Ok
Real time
Control panel
If this option is enabled (option =“YES”), the display provides a value bar showing the
real-time values of the I/O lines of the specified zones during standby status. This
function can be used when the I/O lines are configured as 4-20mA gas lines, and allows
users to view the level of gas detected by each line.
Repeater n
If this option is enabled (option =“YES”), the display provides a value bar showing the
real-time values of the I/O lines of the specified zones during standby status. This
function can be used when the I/O lines are configured as 4-20mA gas lines, and allows
users to view the level of gas detected by each line.