52
Programming from panel
Conventional fire detection control panel
9.2.4 Programming the outputs
From panel: <key>, Programming,
Progr. Output,
select an output,
Ok
This option will allow you to set up the operating mode of each output (RELAY, Expansion board NAC
outputs).
9.2.5 Outputs parameters
INPUT SPRINKLER
The line will operate as a resettable alarm line (it will remain active for the duration of the alarm
condition). Activation of the line will generate a fire alarm and the display will indicate activation
of the “Sprinkler” system. The line will also generate the “Sprinkler” signal that can be used for
the activation of specific outputs which provide separate signals.
Pre-alarm
As above.
NightPrealarm
As above.
Filtered
As above.
INPUT COMMAND
In this mode, the I/O line will operate as a supervised output that when activated will perform the
actions specified below:
Filtered
As above.
Reset
Replicates the
RESET
button on the control panel.
Investigate
Replicates the
INVESTIGATE
button on the control panel.
Silence
Replicates the
SILENCE
button on the control panel.
Toggle day
Inverts the Day/Night operating from Day to Night.
Force night
The control panel will operate in Night mode for the time the input is active.
Evacuate
Functions only when the pre-alarm time is running, in this case the pre-alarm
time will be ignored and the control panel will generate an instant alarm. If
the pre-alarm time is not running, it will have no effect.
INPUT EXTINGUISH
The line will be used to command the extinguishment board functions. The type of command that
is accomplished by activating the line can be set on the line that follows. The available functions
are: "Disable extinguish", "Disable manual", "Disable automatic", "Confirm extinguish", "Manual
extinguish", "Stop extinguish". For further details regarding the previously mentioned functions,
refer to the extinguishant board section.
NC input
If you select "Yes", the standby and alarm intervals will be reversed; for use
with Normally Closed contacts.
Filtered
As above.
Relay, Expansion
NAC..., Power
Stat...
Name of the output you are configuring.
Activation Type
Using the
Ok
key, scroll the various activation types that can be assigned to the output:
OUTPUT ZONE STA-
TUS
In this mode, the output will activate in response to any of the selected signals ("Alarm", "Pre-
alarm", "Gas alarm", "Gas pre-alarm", "Sprinkler", "Supervisory", "Class Change" and "Fault")
relative to the control panel (if the "Panel" option is selected from the following list ), or relative
to the zones specified in the list (All zones set as “YES”).
Silenceable
If “YES” is selected, it will be possible to switch Off the activated output by
inserting the key and pressing the
SILENCE
button.
Inverted
If selected, the output will always be closed to ground and will open when
activated.
Duration
-- min -- sec
Activation time (0 to 10 minutes); if the endurance is not defined (“--”) the
output will not deactivate. Under all circumstances, if the condition clears the
output will deactivate.
At least 1 / 2 /
All
The output will activate if one or more signals activates on at least one/two/
all of the selected zones.