![INIM Electronics SmartLine Series Скачать руководство пользователя страница 11](http://html.mh-extra.com/html/inim-electronics/smartline-series/smartline-series_installation-and-programming-manual_2061464011.webp)
Installation and programming manual
General information
11
2.13 Warranty
INIM Electronics s.r.l. warrants that for a period of 24 months from the date of commissioning, the product
shall be free of defects in materials and workmanship. The warranty applies only to defects in parts and
workmanship relating to normal use. It does not cover:
• Improper use or negligence
• Damage caused by fire, flood, wind or lightning
• Vandalism
• Fair wear and tear
INIM Electronics s.r.l. shall, at its option, repair or replace any defective products. Improper use, that is,
use for purposes other than those mentioned in this manual will void the warranty. For the full details and
conditions regarding the warranty, refer to the purchase order.
2.14 Safety laws
The aim of the instructions in this section is to ensure that the device is installed and handled properly. It is
assumed that anyone who handles this apparatus is familiar with the contents of this chapter.
2.14.1 Compliancy
The design and manufacture of the SmartLine panel conform with EN 54-2
Fire detection and signalling
systems - Control and signalling panels
.
The power supply unit has been especially designed and manufactured in full compliance with EN 54 part 4
Fire detection and fire alarm systems - Power supply equipment.
The SmartLetLoose/ONE extinguishant board enhanced SmartLine control panel has been developed and
designed in compliance with EN 12094-01 Fire-fighting Systems - Components of fire-extinguishant
systems - Part 1: Requirements and testing methods for automatic electrical command and fire-extinguish
or delay management devices.
2.14.2 Managing electronic devices
The normal motions of any person may generate electrostatic potential of thousands of volts. Discharge of this
current through semiconductor devices during handling may cause serious damage which although may not be
immediately evident may reduce the reliability of the circuits.
If located in their housings, the electronic circuits of INIM Electronics products are highly immune to
electrostatic discharge.
Do not expose the circuits to damage by removing the modules unnecessarily from their housings.
• When removing or handling the boards, hold the board edges only.
• Do not touch the electronic components, the printed circuits or the metal parts of the connectors.
• Do not hand the board to another person without first ensuring that both of you have the same
electrostatic potential. This can be achieved by simply shaking hands.
• Place the board on an anti-static surface or a conductor surface with the same potential.
Further information regarding procedures relating to safety when working with electronic devices can be
found in EN 61340-5-1 e CLC/TR 61340-5-2.
2.14.3 Setting up the system
In order to provide adequate protection and instructions for proper use, security professionals (Installers
and maintenance technicians) must be familiar with the operating procedure of this device.
Please read the instructions carefully before installing and setting up this product.
Before first power-up, be sure that the earth connection has been completed properly on the respective
terminal. The recommended minimum wire cross section for the earth connection is 2.5 mm
2
, unless
otherwise stated in accessory documentation.