If a fault appears on screen 3, the message on the second line disappears from the screen, the message on the first line slides down to
the second line and the fault message takes the first line.
!
If a third fault appears on screen 4, the message on the second line disappears from the screen, the message on the first line slides down
to the second line and the third fault message takes the first line.
!
If an alarm appears on screen 4, the message relating to that alarm will not appear.
!
If a new alarm appears on screen 5, the message relating to that alarm will replace the alarm message on the second line.
8.2. RRemoving m
messages oon sscreen
!
If all the faults, displayed on screen or not, are no longer active (circuit-breaker pressed in, emergency stop unlocked, logical input inac-
tive, connection restored, ...), press the Reset button to reset the last fault present on screen or in other words, the last recorded fault. This
way, the previous fault(s) is/are moved forward one line.
The example below shows the screen changes with two faults displayed on screen and one fault not displayed but recorded. In order of
appearance, the following faults are:
- Module 3 CAN
- Emergency stop
- Day tank low fuel level
The three faults are considered as no longer active (fuel level above low level, emergency stop unlocked, CAN connection restored on the
option 3 module).
Messages Fault LLow FFuel LLevel and Fault EEmergency sstop are then displayed. Press Reset to reset the
low fuel level fault (the message disappears).
Ph./ph.
U12
0
voltages
U23
0
(Volts)
U31
0
Fault Low Fuel Level
Fault Emergency Stop
ext command=1 17:45
gen stopped
12/01/00
The message Fault m
module 33 C
CAN then appears on the second line (see screen opposite).
Press Reset to reset the emergency stop fault (the message disappears).
Ph./ph.
U12
0
voltages
U23
0
(Volts)
U31
0
Fault Emergency Stop
Fault module 3 CAN
ext command=1 17:46
gen stopped 12/01/00
The message Fault m
module 33 C
CAN then appears on the second line (see screen opposite).
Press Reset to reset the emergency stop fault (the message disappears).
Ph./ph.
U12
0
voltages
U23
0
(Volts)
U31
0
Fault module 3 CAN
ext command=1 17:47
gen stopped
12/01/00
There are no more faults but is still in Stop mode. As the external command is still available, the ope-
rator must select the Auto mode for the generating set to restart automatically.
Ph./ph. U12
voltages U23
(Volts) U31
ext command=1 17:48
gen stopped
12/01/00
00
00
00
!
An alarm message will automatically disappear when the alarm input is no longer in logical status 1.
99.. D
DIISSPPLLAAYYIIN
NG
G TTH
HEE SSTTAATTU
USS M
MEESSSSAAG
GEESS
All status relating to the operation of the generating set and its auxiliaries are clearly viewed on the two lower lines.
As well as the date and time, the operator will be able to view:
- Operating mode selected (Stop, Manu, Auto, Test)
- Water heater control logical status (active or inactive)
- External command logical status (0 or 1)
- built-in mains failure and mains return delays
- Generating set status (genset on stand-by, stopped or running)
- Engine preglow period
- Cranking period (with attempt number and starter number)
- Starter rest period between two starting attempts, with possible indication of engine preglow
- Starter tripping (indicating starter number)
- RPM and Volts stabilising period
- Authorisation to close the Stand-by contactor in Manu mode
Содержание G 270
Страница 2: ......
Страница 17: ...Alternator 15...
Страница 28: ......
Страница 29: ......
Страница 30: ......
Страница 31: ...User s manual Ingersoll Rand Control unit Intellisys Level 1 1 06F R f constructeur R f GPAO 33502013801...
Страница 57: ......
Страница 58: ......
Страница 121: ......
Страница 122: ...7739614 1 English 04 2002...
Страница 123: ......
Страница 124: ......
Страница 125: ...EDITION JUNE2002 CPN 85623031 33519009601 ind1 GENERATOR PARTS LISTS GENERATOR MODEL G270...
Страница 151: ...G270 EDITION JUNE2002 27...
Страница 184: ......
Страница 185: ......
Страница 186: ......
Страница 212: ...26 INSTALLATION AND MAINTENANCE LSA 46 2 47 1 ALTERNATORS SPARE PARTS Ref 2981 GB 4 33 a 04 00 LEROY SOMER...
Страница 213: ...27 INSTALLATION AND MAINTENANCE LSA 46 2 47 1 ALTERNATORS SPARE PARTS Ref 2981 GB 4 33 a 04 00 LEROY SOMER...
Страница 214: ...MOTEURS LEROY SOMER 16015 ANGOUL ME CEDEX FRANCE Imprimerie MOTEURS LEROY SOMER RC ANGOULEME B 671 820 223...