30
XtrapulsEasy
™-DB - Installation Guide
Chapter 5 - Appendix
Damage
Action
Periodicity
Cooling
Check the room temperature of the drive
Every year
Dust
Check connectors, and cabinet cooling system
Every year
Corrosion
Check housing and electrical connection
Every year
Mechanical mounting
- Check the correct drive fastening
- Check the tightening of the electrical connection
Every year
5.3.2 - Warranty
Any intervention on the board will cancel the warranty
5.4 - OPERATING ENVIRONMENT CONDITIONS
A
-
CLIMATIC CONDITIONS
1
-
Cooling fluid temperature
Air : -25°C to +40° C
2
-
Air temperature
-25°C to +40°C
3
-
Relative moisture
5% to 85%
without condensation
4
-
Dust and particles
Clean air (pollution degree 2)
Drive must be protected against conducting dust
5
-
Storage periods
no restriction
B
-
MECHANICAL INSTALLATION CONDITIONS
The drive must be mounted on a stiff surface, in rooms or additional housings without hindering the heatsink.
The reliability may be increased by installing a cooling system (take care of condensation).
Other installation conditions must be specially analysed and subjected to a technical specification in
agreement with INFRANOR.
Vibration level for Xtrapuls
Easy™-ak-60/45-DB
The Xtrapuls
Easy™-ak-60/45-DB drive can be integrated in mobile equipment which vibration level is up to 4g.
Frequency (Hz)
Amplitude (mm)
Acceleration (g)
5
f < 25
4,95
not applicable
25
f < 1000
not applicable
4
The validation profile is shown below:
Definition of the stress axes:
Endurance template:
16 sweeps during 2 hours in each axis
Z
Y
X
Hz
G
4
0
5
25
1000