5-13
5.2 Overview of Function Codes
This section provides an overview of the function codes frequently used for the Jaguar CUB series of
inverter.
F00
Data Protection
Specifies whether function code data is to be protected from being accidentally
changed by keypad operation. If data protection is enabled (F00 = 1),
or
key
operation to change data is disabled so that no function code data, except F00 data,
can be changed from the keypad. To change F00 data, simultaneous keying of
+
keys is required.
F01, C30
Frequency Command 1 and 2
Selects the devices to set the set frequency 1 for driving the motor.
Set F01 to:
To do this
0
Enable the
and
keys on the built-in keypad. (Refer to
Chapter 3 "OPERATION USING THE KEYPAD.")
1
Enable the voltage input to terminal [12] (0 to +10 VDC, maximum
frequency obtained at +10 VDC).
2
Enable the current input to terminal [C1] (+4 to +20 mA DC,
maximum frequency obtained at +20 mA DC).
3
Enable the sum of voltage and current inputs to terminals [12] and
[C1]. See the two items listed above for the setting range and
maximum frequencies.
Note: If the sum exceeds the maximum frequency, the maximum
frequency will apply.
4
Enable the built-in potentiometer (POT). (Maximum frequency
obtained at full scale of the POT)
• There are other frequency command means (such as the communi-
cations facility, multistep frequency, etc.) with higher priority than that
of F01.
• For frequency commands by terminals [12] (voltage) and [C1] (cur-
rent) and by the built-in potentiometer, setting the gain and bias
changes the relationship between those frequency commands and the
drive frequency to enable matching your system requirements. Refer
to function code F18 for details.
• For the inputs to terminals [12] (voltage) and [C1] (current), low-pass
filters can be enabled. Refer to function codes C33 and C38 for de-
tails.
In addition to "F01 Frequency command 1," "C30: Frequency command 2" is also
available. To switch them, use the terminal command (Hz2/Hz1). For details of the
(Hz2/Hz1), refer to "E01 to E03: Command Assignment to Terminals [X1] to [X3]."
Содержание Jaguar CUB
Страница 47: ...3 5 Figure 3 2 Alarm Mode Status Transition...
Страница 77: ...5 4...
Страница 78: ...5 5 E codes Extension Terminal Functions...
Страница 80: ...5 7...
Страница 81: ...5 8 C codes Control Functions of Frequency...
Страница 84: ...5 11 y codes Link Functions...
Страница 149: ...8 5 8 3 Common Specifications...
Страница 150: ...8 6...
Страница 153: ...8 9 8 5 External Dimensions 8 5 1 Standard Models...
Страница 154: ...8 10...
Страница 155: ...8 11 8 5 2 Models Available on Order EMC Filter Built in Type...
Страница 156: ...8 12...