(3)  Use shielded wires for the control signals of the inverter to input to/output from the control 

terminals. Firmly clamp the control wire shields to the EMC grounding flange (in the same way 
as the motor cables). 

Figure 10.2  Connecting Shielded Cables 

(4)  If noise from the inverter exceeds the permissible level, enclose the inverter and its 

peripherals within a metal enclosure as shown in Figure 10.3. 

Figure 10.3  Installing the Inverter into a Metal Enclosure 

Содержание Jaguar CUB

Страница 1: ...is instruction manual and be familiar with the handling procedure for correct use Improper handling blocks correct operation or causes a short life or failure Deliver this manual to the end user of th...

Страница 2: ...produced or copied without prior written permission from IMO Precision Controls Ltd All products and company names mentioned in this manual are trademarks or registered trademarks of their respective...

Страница 3: ...ase induction motor Read through this instruction manual and be familiar with the handling method for correct use Improper handling blocks correct operation or causes a short life or failure Have this...

Страница 4: ...or substantial property damage Failure to heed the information contained under the CAUTION title can also result in serious con sequences These safety precautions are of utmost importance and must be...

Страница 5: ...the related current range Use wires in the specified size Otherwise fire could occur Do not use one multicore cable in order to connect several inverters with motors Do not connect a surge killer to t...

Страница 6: ...is ensured even in such cases Otherwise an accident could occur The STOP key is only effective when function setting Function code F02 has been es tablished to enable the STOP key Prepare an emergency...

Страница 7: ...is unlit and check the DC link circuit voltage across the P and N terminals to be lower than 25 VDC Otherwise electric shock could occur Maintenance inspection and parts replacement should be made on...

Страница 8: ...ates the power supply lines connected to the electric equipment using an isolation transformer 4 The inverter should be used in an environment that does not exceed Pollution Degree 2 requirements If t...

Страница 9: ...ture of 40qC 3 Wire sizes are calculated on the basis of the input current under the condition that the power supply capacity and impedance are 500 kVA and 5 respectively Recommended wire size mm2 1 R...

Страница 10: ...wire only for control circuits 5 Field wiring connection must be made by a UL Listed and CSA Certified closed loop terminal connector sized for the wire gauge involved Connector must be fixed using t...

Страница 11: ...M1 2 TERM2 1 TERM2 2 Class J fuse current A CUB3A 2 10 CUB5A 2 10 6 1 2 15 CUB8A 2 20 CUB11A 2 14 30 Three phase 200V CUB17A 2 15 9 1 8 3 5 0 4 1 8 0 2 10 20 0 5 40 CUB1A5 4 3 CUB2A5 4 6 CUB3A7 4 10 C...

Страница 12: ...unning general purpose motors Noise When an inverter is used with a general purpose motor the motor noise level is higher than that with a commercial power supply To reduce noise raise carrier frequen...

Страница 13: ...e primary circuit of the inverter to protect the wiring Ensure that the circuit breaker capacity is equivalent to or lower than the recommended capacity Installing an MC in the secondary circuit If a...

Страница 14: ...ire Wiring length between inverter and motor If long wiring is used between the inverter and the motor the inverter will overheat or trip as a result of overcurrent high frequency current flowing into...

Страница 15: ...N CODES This chapter provides a list of the function codes Function codes to be used often and irregular ones are described individually Chapter 6 TROUBLESHOOTING This chapter describes troubleshootin...

Страница 16: ...n result in the inverter not operating to full efficiency as well as information concerning incorrect operations and settings which can result in accidents This icon indicates information that can pro...

Страница 17: ...d Checking 4 1 4 1 3 Preparation before running the motor for a test Setting function code data 4 2 4 1 4 Test run 4 3 4 2 Operation 4 3 Chapter 5 FUNCTION CODES 5 1 5 1 Function Code Tables 5 1 5 2 O...

Страница 18: ...mpliance with the Low Voltage Directive in the EU 10 5 10 5 1 General 10 5 10 5 2 Points for Consideration when using the Jaguar CUB series in a system to be certified by the Low Voltage Directive in...

Страница 19: ...e phase 200v 8A 8 Amps 4 Three phase 400v 11A 11 Amps 17A 17 Amps 1A5 1 5 Amps 2A5 2 5 Amps 3A7 3 7 Amps 5A5 5 5 Amps 9A 9 Amps Note When None and w o braking resistor standard are selected in the bui...

Страница 20: ...always support its bottom at the front and rear sides with both hands Do not hold covers or individual parts only You may drop the inverter or break it Avoid applying excessively strong force to the...

Страница 21: ...erter in an airtight vinyl sheet or the like for storage 3 If the inverter is to be stored in an environment with a high level of humidity put a drying agent such as silica gel in the airtight package...

Страница 22: ...inverter on a base constructed from metal or other non flammable material A fire may result with other material 2 Clearances Ensure that the minimum clearances indicated in Figure 2 1 are maintained a...

Страница 23: ...down or horizontally Doing so will reduce the heat dissipation efficiency of the inverter and cause the overheat protection function to operate so the inverter will not run Prevent lint paper fibers...

Страница 24: ...rcuit 1 Arrangement of the main circuit terminals Table 2 3 Main Circuit Terminals Power supply voltage Applicable motor rating kW Inverter type Terminal screw size Tightening torque N m Refer to 0 4...

Страница 25: ...o 0 75 mm2 5 to 7 mm 1 7 mm W x 1 6 mm H Manufacturer of stick terminals WAGO Company of Japan Ltd Refer to Table 2 5 Table 2 5 Recommended Stick Terminals Type 216 Screw size Wire size With insulated...

Страница 26: ...75 CUB2A5 4 1 5 CUB3A7 4 2 2 CUB5A5 4 Three phase 400 V 4 0 CUB9A 4 2 0 2 0 2 5 2 0 2 0 2 5 2 0 2 0 2 5 2 0 2 0 2 5 2 0 2 0 2 5 0 4 CUB3A 1 0 75 CUB5A 1 2 0 2 0 2 5 1 5 CUB8A 1 2 0 2 0 2 5 2 0 3 5 4...

Страница 27: ...ker ELCB with the exception of those exclusively designed for protection from ground faults in the path of power lines Use the devices within the re lated current range Use wires in the specified size...

Страница 28: ...als G d Inverter output terminals U V and W e DC reactor connection terminals P1 and P f Braking resistor connection terminals P and DB g DC link circuit terminals P and N h Main circuit power input t...

Страница 29: ...D or C grounding work has been completed respectively in compli ance with the Electric Facility Technical Standard 2 Connect a thick grounding wire with a large surface area and which meets the ground...

Страница 30: ...r to protect the motor from overheating the thermal relay may malfunction even with a wiring length shorter than 50 m In this situation add an output circuit filter option or lower the carrier frequen...

Страница 31: ...uired The wiring length should be 10 m or below If both a DC reactor and a braking resistor are to be connected to the inverter secure both wires of the DC reactor and braking resistor together to ter...

Страница 32: ...ith the jumper bar 2 Put the wire from terminal P of the braking resistor and the jumper bar on terminal P in this order then secure them with the screw removed in 1 above 3 Tighten the screw on termi...

Страница 33: ...tion of those exclusively designed for protection from ground faults Figure 2 10 Main Circuit Power Input Terminal Connection It is recommended that a manual on off magnetic contactor be connected Thi...

Страница 34: ...ed from the inverter motor and wires Implement appropriate measure to prevent the nearby sensors and devices from malfunctioning due to such noise An accident could occur Figure 2 12 Example of Contro...

Страница 35: ...e 22 k Allowable maximum input voltage is 15 VDC If the input voltage is 10 VDC or more the inverter will limit it at 10 VDC C1 Current input 1 The frequency is set according to the external analog in...

Страница 36: ...ed in the circuit Do not con nect the relay s contact to terminal 11 When the inverter is connected to an external device outputting the analog signal a malfunction may be caused by electric noise gen...

Страница 37: ...tion codes E01 to E03 E98 and E99 For details refer to Chapter 5 Section 5 2 Overview of Function Codes 2 Input mode i e Sink Source is changeable by using the internal jumper switch 3 Switches the lo...

Страница 38: ...evice To do so switch the jumper to SINK Figure 2 15 External Power Supply Connection If the jumper switch is set at SOURCE Connecting a relay to the inverter Figure 2 16 a Relay Connection Connecting...

Страница 39: ...de E20 Refer to Chapter 5 Section 5 2 Overview of Func tion Codes for details 2 Switches the logic value 1 0 for ON OFF of the terminals between Y1 and Y1E If the logic value for ON between Y1 and Y1E...

Страница 40: ...dard inverters equipped with an RS485 communications card option Route the wiring of the control terminals as far from the wiring of the main circuit as possible Otherwise electric noise may cause mal...

Страница 41: ...ere is high voltage electronic devices on the RS485 communications card Doing so could cause electric shock 2 3 10 Replacing the Control Circuit Terminal Block TB Cover Upon completion of the wiring o...

Страница 42: ...ter Mount the inverter onto a metal board and connect the whole board to the ground Connect an EMC filter to the inverter power wires 3 When implementing measures against noise generated from peripher...

Страница 43: ...key to run the motor STOP key Press this key to stop the motor UP DOWN keys Press these keys to select the setting items and change the function data displayed on the LED monitor Program Reset key wh...

Страница 44: ...atus in realtime Programming mode This mode allows you to set function code data and check a variety of information relating to the inverter status and maintenance Alarm mode If an alarm occurs the in...

Страница 45: ...uency 1 P_ _ P codes Motor parameters 1 H_ _ H codes High performance functions 1 J_ _ J codes Application functions 1 Data setting 1 y_ _ y codes Link functions Selecting each of these function codes...

Страница 46: ...e key when the alarm code is displayed Displaying the Alarm History It is possible to display the most recent 3 alarm codes in addition to the one currently displayed Previous alarm codes can be displ...

Страница 47: ...3 5 Figure 3 2 Alarm Mode Status Transition...

Страница 48: ...topping and Rotational Direction and key If Function code F02 is set to Pressing the key ro tates the motor 2 in the forward direction 3 in the reverse direction For setting 0 or 1 to F02 refer to Cha...

Страница 49: ...ncy and others with the and keys the lowest digit on the display will blink Change the setting starting with the lowest digit and the blinking digit cursor will move to the next upper digit If you pre...

Страница 50: ...ched to any other PID process command entry and then returned to the keypad entry the setting will be retained Further even turning off the inverter will automatically save the setting into the non vo...

Страница 51: ...splayed Value Speed monitor Hz rpm m min min 50 00 Refer to Table 3 4 Output current A 1 90A Detected output current A An alternative expression for A ampere Input power kW 0 40P Detected input curren...

Страница 52: ...ine speed m min and constant rate of feeding time min which can be selected by setting up function code E48 2 These PID related information will appear only when the inverter is under the PID control...

Страница 53: ...iven below c Making the inverter ready for jogging The JoG appears on the LED monitor 1 Switch to Running mode Refer to page 3 2 for details 2 Press the keys at the same time simultaneous keying The L...

Страница 54: ...or parameters P02 to P99 Motor parameters To be used to set special parameters for the motor capacity etc H codes High performance functions H03 to H98 High level functions To be used for high added v...

Страница 55: ...3 13 Figure 3 4 shows the status transition for Menu 1 Data setting and Figure 3 5 shows an example of the function code data changing procedure Figure 3 4 Data Setting Status Transition...

Страница 56: ...ress the key In this example select function code F 01 The data of this function code will appear In this example data 4 of F 01 will appear 4 Change the function code data using the and keys In this...

Страница 57: ...e data and change again if necessary Figure 3 6 shows the status transition diagram for Data checking To check function codes in Menu 2 Data checking it is necessary to set function code E52 data to 1...

Страница 58: ...ot switch the menu to any other one set function code E52 data to 2 Full menu mode Figure 3 7 Drive Monitoring Status Transition Basic key operation 1 With the menu displayed use the and keys to selec...

Страница 59: ...min The unit for load shaft speed is rpm and that for line speed is m min Display value Output frequency Hz before slip compensation u Function code E50 appears for 10000 rpm or m min or more When ap...

Страница 60: ...n the DC link circuit voltage is higher than the undervoltage level 12 RL 1 when communication is effective when run commands and set frequencies commands are issued via communications 4 BRK Always 0...

Страница 61: ...expres sion The hexadecimals are shown as they appear on the LED monitor Table 3 9 Binary and Hexadecimal Conversion Binary Hexadecimal Binary Hexadecimal 0 0 0 0 0 1 0 0 0 8 0 0 0 1 1 1 0 0 1 9 0 0 1...

Страница 62: ...code E52 data to 2 Full menu mode Figure 3 8 I O Checking Status Transition Basic key operation 1 With the menu displayed use the and keys to select I O check 4 _o 2 Press the key to display the code...

Страница 63: ...displayed with ON OFF of the LED segment or in hexadecimal display Display I O signal status with ON OFF of the LED Segment As shown in Table 3 11 and the figure below segments a to e on LED1 light w...

Страница 64: ...closed For example if Y1 is on and the circuit between 30A and 30C are short circuited with each other then the display for LED4 to LED1 would be 0101 How the hexadecimal display is configured for th...

Страница 65: ...h the menu to any other one set function code E52 data to 2 Full menu mode Figure 3 9 Maintenance Information Status Transition Basic key operations 1 With the menu displayed use the and keys to selec...

Страница 66: ...However when the total time exceeds 65 535 hours the count stops and the display remains at 65 53 5_07 Accumulated run time of the cooling fan Shows the accumulated run time of the cooling fan The coo...

Страница 67: ...rations 1 With the menu displayed use the and keys to select Alarm information 6 AL 2 Press the key to display the alarm list code e g 1 OL1 In the list of alarm codes the alarm information for last 4...

Страница 68: ...er run command is set to on are calculated and displayed 1 000 indicates 1 000 times When any number from 0 001 to 9 999 is displayed the display increases by 0 001 per startup and when any number fro...

Страница 69: ...6_20 Terminal output signal status under commu nication control in hexadecimal for mat Shows the ON OFF status of the digital I O terminals under communication control Refer to Displaying control I O...

Страница 70: ...quipment 5 Turn the switches off so that the inverter does not start or operate erroneously at power on 6 Check if safety measures are taken against runaway of the system e g a defense to protect peop...

Страница 71: ...me Function code data Factory setting F 04 Base frequency 60 0 50 0 Hz Note F 05 Rated Voltage at base frequency 0 V Output voltage interlocked with the source voltage P 02 Motor Parameter Rated capac...

Страница 72: ...e LED monitor blinks while indicating the 0 00 Hz frequency 2 Rotate the built in potentiometer clockwise set the frequency to a low frequency such as 5 Hz Check that set frequency blinks on the LED m...

Страница 73: ...emory To save the change press the key If you press the key without pressing the key to exit the current state then the changed data will be discarded and the previous data will take effect for the in...

Страница 74: ...tput frequency F11 sets the operation level of the electronic thermal function to the current value Set approximately 1 0 to 1 1 multiples of the allowable continuous current rated current of the moto...

Страница 75: ...logic system for an I O signal terminal display data of 1000s by adding 1000 to the data for the normal logic in the corresponding function code and then press the key For example if a coast to stop c...

Страница 76: ...1 Standard torque boost Nominal rated current of standard motor and Nominal rated capacity of standard motor differ depending upon the rated input voltage and rated capacity Refer to Table 5 1 Standar...

Страница 77: ...5 4...

Страница 78: ...5 5 E codes Extension Terminal Functions...

Страница 79: ...series of inverters does not recognize these codes 1 Standard torque boost Nominal rated current of standard motor and Nominal rated capacity of standard motor differ depending upon the rated input v...

Страница 80: ...5 7...

Страница 81: ...5 8 C codes Control Functions of Frequency...

Страница 82: ...rmance Functions Standard torque boost Nominal rated current of standard motor and Nominal rated capacity of standard motor differ depending upon the rated input voltage and rated capacity Refer to Ta...

Страница 83: ...5 10 Note Function codes H71 and H95 appear on the LED monitor however the Jaguar CUB series of inverters does not recognize these codes J codes Application Functions...

Страница 84: ...5 11 y codes Link Functions...

Страница 85: ...tandard motor A Nominal rated capacity of standard motor kW Power supply voltage Applicable motor rating kW Function code F09 Function codes F11 E34 and P03 Function code P02 0 4 7 1 2 30 0 4 0 75 6 8...

Страница 86: ...Enable the sum of voltage and current inputs to terminals 12 and C1 See the two items listed above for the setting range and maximum frequencies Note If the sum exceeds the maximum frequency the maxim...

Страница 87: ...cify the motor rotational direction assign the commands FWD and REV to terminals FWD and REV respectively Turn on the FWD or REV for the forward or reverse direction respectively If both of FWD and RE...

Страница 88: ...equency F05 Set 0 or the rated voltage printed on the nameplate labeled on the motor If 0 is set the inverter supplies voltage equivalent to that of the power source of the inverter at the base freque...

Страница 89: ...tage Furthermore setting the non linear V f pattern using function codes H50 and H51 allows patterns with higher or lower voltage than that of the normal pattern to be defined at an arbitrary point in...

Страница 90: ...en if the load varies assuring stable motor operation Variable torque characteristics F37 0 Constant torque characteristics F37 1 Set an appropriate torque boost rate that will keep the starting torqu...

Страница 91: ...auto energy saving operation may be brought about The auto energy saving operation is designed for use with the frequency lower than the base frequency If the frequency becomes higher than the base fr...

Страница 92: ...tput frequency and stops its output to make the motor to coast to a stop When the power is recovered with any run command being on the inverter will restart at the saved frequency During the instantan...

Страница 93: ...tart at the starting frequency preset by the related function codes The ex ternal circuitry should be configured so that it is able to issue any run command within 2 seconds or so that it features a m...

Страница 94: ...ombining the settings for bias F18 bias reference point C50 gains C32 and C37 and gain reference points C34 and C39 As illustrated in the graph below the relationship between the set frequency and ana...

Страница 95: ...Therefore the bias is 0 F18 0 Since 1 V is the bias reference point and it is equal to 10 of 10 V then the bias reference point should be 10 C50 10 Point B If the analogue input is at 5 V the set freq...

Страница 96: ...cy At the startup of an inverter the initial output frequency is equal to the starting fre quency The inverter stops its output at the stop frequency Set the starting frequency to a level that will en...

Страница 97: ...or running sound tone This setting is effective when the carrier frequencies set to function code F26 is 7 kHz or lower Changing the tone level may reduce the high and harsh running noise from the mot...

Страница 98: ...ating the output gain which is required for outputting the voltage V V via terminal FMA when current I A flows across the inverter 100 V 10 V V A A 2 gain Output ref u u u I I Iref A Reference current...

Страница 99: ...ased on the reference current Iref A as shown below 100 A A Setting ref limit u I I Example Setting the current limiting level Ilimit at 4 2 A for 0 75 kW standard motors 84 100 A 5 0 A 4 2 Setting u...

Страница 100: ...F50 and F51 respec tively Those values differ depending upon the specifications of the braking resistor Refer to the tables on the next page Depending on the discharging capability margin of a braking...

Страница 101: ...Q ty Resis tance Cap acity W Discharg ing capability kWs Braking time s Allowable average loss kW Duty cycle ED CUB3A 2 250 37 CUB5A 2 See IMO 100 200 50 133 0 075 20 CUB8A 2 73 14 CUB11A 2 See IMO 40...

Страница 102: ...ncies With this the inverter may drive the motor at 8 different preset speeds The table below lists the frequencies that can be obtained by the combination of switching SS1 SS2 and SS4 In the Selected...

Страница 103: ...t the alarm output on terminals Y1 and 30A B C Opening the circuit will re lease all the alarm indications to restart operation Allow 10 ms or more for the short circuit time RST should be kept off fo...

Страница 104: ...ommand on allows the frequency command 2 to be se lected Enable editing of function code data from the keypad WE KP Function code data 19 Turning off the WE KP command prohibits changing of function c...

Страница 105: ...he frequency command or drive command given via the RS485 communica tions facility defined by function code H30 If the LE command is not assigned to any terminal the inverter will interpret LE as bein...

Страница 106: ...quent on off operations If frequent signal outputs are ex pected e g assigning any current limiter signal and activating the current limiter actively then use Y1 For rare signal outputs e g for invert...

Страница 107: ...This signal is used to issue a motor overload early warning for enabling you to take corrective action before the inverter detects a motor overload OL1 alarm and stops its output The motor temperatur...

Страница 108: ...ptions of function code H70 Current detection ID Function code data 37 This signal is turned on when the output current exceeds the operation level specified by function code E34 and stays in this sta...

Страница 109: ...nditions beforehand Set C21 to 1 to enable timer operation To display the timer count on the LED monitor set function code E43 LED monitor to 13 Timer count Set up the frequency for the timer operatio...

Страница 110: ...otor speed Typical rated slip frequencies for 100 Rated capacity kW HP Standard motors Hz Typical motors rated in HP Hz Conventional motors Hz Other motors Hz 0 06 0 1 1 77 2 50 1 77 1 77 0 1 0 12 1 7...

Страница 111: ...sary to press the and keys or the and keys simultaneously If H03 is set to Function 0 Disable initialization Settings made by the user manually will be retained 1 Initialize all function code data to...

Страница 112: ...0 15 00 3 71 to 5 50 5 5 22 00 22 00 22 00 Three phase 200V Single phase 200V 5 51 to 10 00 7 5 29 00 29 00 29 00 0 01 to 0 06 0 06 0 22 0 22 0 22 0 07 to 0 10 0 1 0 34 0 34 0 34 0 11 to 0 20 0 2 0 65...

Страница 113: ...7 5 18 60 Three phase 200V Single phase 200V 7 51 to 10 00 10 25 30 0 01 to 0 10 0 1 0 22 0 11 to 0 12 0 12 0 34 0 13 to 0 25 0 25 0 70 0 26 to 0 50 0 5 1 00 0 51 to 1 00 1 1 50 1 01 to 2 00 2 2 90 2...

Страница 114: ...LED monitor display Instantaneous over current protection OC1 OC2 or OC3 Braking resistor over heated dbH Overvoltage protection OU1 OU2 or OU3 Motor overloaded OL1 Heat sink overheated OH1 Inverter...

Страница 115: ...celeration deceleration To reduce the impact on the inverter driven motor during acceleration deceleration the inverter gradually accelerates decelerates the motor in both the accelera tion decelerati...

Страница 116: ...ate hunting or making the inverter enter the OU alarm mode and trip When setting the acceleration time therefore you need to take into account the load condition and moment of inertia H69 Regenerative...

Страница 117: ...the inverter output frequency drops as it will have no effect If the following functions to limit the output current are enabled F43 z 0 and H12 1 this control does not work H96 Priority on STOP Key...

Страница 118: ...tected in the three phase input power source the inverter will enter Alarm mode and issue an alarm L This prevents the inverter from un dergoing heavy stress that may be caused by input phase loss or...

Страница 119: ...output terminals U V and W Some electric charge may remain in the DC bus capacitor even after the power is turned off Therefore it may take some time until the DC link circuit voltage reaches a safe l...

Страница 120: ...14 OU1 OLU Overload protection p 6 15 OU2 E 1 Memory error p 6 15 OU3 Overvoltage protection p 6 10 E 2 Remote keypad communications error p 6 16 LU Undervoltage protection p 6 10 E 3 CPU error p 6 1...

Страница 121: ...rotation direction command with Menu 4 I O checking using the keypad Input the rotation direction F02 0 or select the keypad operation with which the rotation direction is fixed F02 2 or 3 4 The inver...

Страница 122: ...that the output current is not too large Reduce the load e g operate the mechanical brake correctly Check that the motor starts running if the value of torque boost F09 is increased Increase the value...

Страница 123: ...ue boost F09 then turn the power off and back on again and check if the speed increases Adjust the value of the torque boost F09 7 The current limiting operation did not increase the output frequency...

Страница 124: ...ration Readjust the data of the oscillation suppression gain H80 currently set 4 The vibration system having low stiffness in a load caused hunting or the current is irregular due to special motor con...

Страница 125: ...did not make the motor restart even if the power recovered after an instantaneous power failure Check if an undervoltage trip occurs Change the data of function code F14 to 4 or 5 2 The run command s...

Страница 126: ...1 The limiting menus function was not selected appropriately Check the data of function code E52 Change the data of function code E52 to display the desired menu 3 Nothing appears on the LED monitor P...

Страница 127: ...dge if the trend is over the calculated load value for your system design If the load is too heavy decrease it or raise the inverter capacity 3 Loads were too heavy Trace the current trend and check i...

Страница 128: ...it voltage exceeds the overvoltage suppression level the inverter changes the deceleration time to three times longer than the set value Set the rated voltage at base frequency F05 to 0 to improve bra...

Страница 129: ...sh current caused the power voltage drop because power transformer capacity was insufficient Check if the alarm occurs when you switch on a molded case circuit breaker an earth leakage circuit breaker...

Страница 130: ...es 1 Temperature around the inverter exceeded that of inverter specifications Measure the temperature around the inverter Lower the temperature around the inverter e g ventilate the enclosure well Red...

Страница 131: ...the load 2 Cooling system for the motor malfunctioned Check if the cooling system is operating normally Repair or replace the cooling system 3 Load was too heavy Measure the output current Reduce the...

Страница 132: ...if the surface temperature itself does not rise the alarm may be detected if the resistor is used more frequently than the set data of function codes F50 and F51 If you use the resistor to the limit...

Страница 133: ...verload occurs using the overload early warning E34 Decrease the carrier frequency F26 Enable overload protection control H70 5 The acceleration deceleration time was too short Recalculate the require...

Страница 134: ...the inverter Possible Causes What to Check and Suggested Measures 1 Break in the communications cable or poor contact Check continuity of the cable contacts and connections Replace the cable 2 A high...

Страница 135: ...ures 1 Host controllers e g PLCs and personal computers did not operate due to incorrect settings and or defective software hardware Check the controllers Remove the cause of the controller error 2 Re...

Страница 136: ...cuit voltage to drop to the preset voltage when the power is turned off Remove whatever is causing the rapid discharge of the electric charge After pressing the key and releasing the alarm reset the d...

Страница 137: ...parts replacement should be made only by authorized persons Take off watches rings and other metallic matter before starting work Use insulated tools Never attempt to repair the Inverter Electric shoc...

Страница 138: ...pection 1 2 The display can be read and there is no fault Structure such as frame and cover 1 Abnormal noise and excessive vibration 2 Loosen bolts tightened parts 3 Deformation and breakage 4 Discolo...

Страница 139: ...on 2 Visual inspection 1 2 No abnormalities Control circuit Printed circuit board Note 1 1 Check for loose screws and connectors 2 Check for odor and discoloration 3 Check for cracks breakage deformat...

Страница 140: ...s The capacitance is displayed in the reduction ratio of the initial value written in the inverter memory before shipment Capacitance measurement procedure 1 Remove the RS485 communications card optio...

Страница 141: ...on the LED monitor Use this to determine when the capacitor should be replaced The display is in units of 1000 hours 3 Cooling fan The inverter accumulates hours for which the cooling fan has run The...

Страница 142: ...Three phase input Single phase input 100 A t V Curren Voltage 3 W power Electric factor Power 100 A t V Curren Voltage W power Electric factor Power Table 7 3 Meters for Measurement of Main Circuit I...

Страница 143: ...control wiring 3 Connect the main circuit terminals with a common cable as shown in Figure 7 2 4 The Megger test must be limited to across the common line of the main circuit and the ground terminal G...

Страница 144: ...e following information to the Company where you purchased the product or contact IMO 1 Inverter type 2 SER No serial number of equipment 3 Function codes and their data that you changed 4 ROM version...

Страница 145: ...If this value is 2 to 3 use an AC reactor ACR 6 Tested under the standard load condition 85 load for applicable motor rating 7 Calculated under specified conditions 8 Indicates the value when using a...

Страница 146: ...icable motor rating 6 Calculated under specified conditions 7 Indicates the value when using a DC reactor option 8 Average braking torque obtained with the AVR control off F 05 0 Varies according to t...

Страница 147: ...licable motor rating 6 Calculated under specified conditions 7 Indicates the value when using a DC reactor option 8 Average braking torque obtained with the AVR control off F 05 0 Varies according to...

Страница 148: ...V 4 three Phase 400 V Note 2 A box in the above table replaces the E suffix for the filtered version Other than those items in the above table are the same as those in Section 8 1 Standard Models Sin...

Страница 149: ...8 5 8 3 Common Specifications...

Страница 150: ...8 6...

Страница 151: ...e ensure that the circuit breaker capacity is equivalent to or lower than the recommended capacity Note 2 A magnetic contactor MC should if necessary be mounted independent of the MCCB or ELCB to cut...

Страница 152: ...nd 11 Note 6 For the wiring of the control circuit use shielded or twisted wires When using shielded wires connect the shields to G To prevent malfunction due to noise keep the control circuit wiring...

Страница 153: ...8 9 8 5 External Dimensions 8 5 1 Standard Models...

Страница 154: ...8 10...

Страница 155: ...8 11 8 5 2 Models Available on Order EMC Filter Built in Type...

Страница 156: ...8 12...

Страница 157: ...is function prevents the inverter from undergoing heavy stress that may be caused by input phase loss or interphase voltage unbalance exceeding 6 and may damage the inverter If connected load is light...

Страница 158: ...tput for any fault The inverter outputs a relay contact signal when the inverter issues an alarm and stops the inverter output Alarm Reset The alarm stop state is reset by pressing the key or by the d...

Страница 159: ...is given when Powering up Releasing an alarm key turned on Link command LE has switched inverter operations E 6 Yes RS485 communication error On detecting an RS485 communication error the inverter di...

Страница 160: ...N for single phase power from overload or short circuit which in turn prevents secondary disasters caused by the inverter malfunctioning RCDs ELCBs function in the same way as MCCBs Use the MCCBs and...

Страница 161: ...er source side cannot cut it off for maintenance or inspection purpose For the purpose only it is recommended that you use an MC capable of turning the MC on off manually Note When your system require...

Страница 162: ...factor correction harmonic component reduction Generally a capacitor is used to correct the power factor of the load however it cannot be used in a system that includes an inverter Using a DCR increa...

Страница 163: ...unications card This makes communication to a PLC or personal computer system possible Options for Operation and Communications Inverter support loader software Inverter support loader software Window...

Страница 164: ...ines described on page viii 10 2 Compliance with European Standards The CE marking on IMO products indicates that they comply with the essential requirements of the Electromagnetic Compatibility EMC D...

Страница 165: ...isfy the requirements noted above use the EMC filter built in type of inverters according to the descriptions contained in this instruction manual Installing the inverter s in a metal enclosure may be...

Страница 166: ...ontrol wire shields to the EMC grounding flange in the same way as the motor cables Figure 10 2 Connecting Shielded Cables 4 If noise from the inverter exceeds the permissible level enclose the invert...

Страница 167: ...to power lines are strictly regulated as stated below If an inverter whose rated input is 1 kW or less is connected to low voltage commercial power lines it is regulated by the harmonics emission regu...

Страница 168: ...er To obtain the data contact IMO Note 1 Boxes in the table above replace E suffix for Filtered version 2 When supplying three phase 200 VAC power stepped down from a three phase 400 VAC power line us...

Страница 169: ...in the handling setting up and operating of the Jaguar CUB series of inverters Please feel free to send your comments regarding any errors or omissions you may have found or any suggestions you may ha...

Страница 170: ...IMO Precision Controls Ltd Automation and Controls 1000 North Circular Road Staples Corner London NW2 7JP United Kingdom Phone 44 0 20 8452 6444 Fax 44 0 20 8450 2274 URL http www imopc com...

Отзывы: