5-39
P99
Motor Selection
To use automatic control features (e.g., the auto torque boost/auto energy saving
and slip compensation) or overload protection for the motor (electronic thermal), the
inverter invokes the parameters and characteristics of the motor. To match the
driving characteristics between the inverter and motor, set the motor characteristics
with this function code and set H03 to "2" to initialize the motor parameter. This
action automatically updates the data of function codes P03, P09 and the constants
used inside the inverter.
Motors P99
=
Standard motors
0
Typical motors rated in HP
1
Conventional motors
3
Other motors
4
• For other motors (P99 = 4), the parameters for a standard motor may
be applicable.
• The inverter also supports motors rated by HP (horse power: typical in
the North America area, P99 = 1).
H03
Data Initialization
Initializes the current function code settings to the factory defaults or initializes the
motor constants (parameters).
To change the H03 data, it is necessary to press the
and
keys or the
and
keys simultaneously.
If H03 is set to:
Function
0
Disable initialization
(Settings made by the user manually will be retained.)
1
Initialize all function code data to the factory defaults
2
Initialize the P03 data (Rated current of the motor) and inter-
nally used constants to the motor constants determined by P02
data (Motor capacity) and P99 (Motor characteristics), as listed
on the next page.
Initialize P09 data (Slip compensation gain) to 0.0.
To initialize the motor constants, set the related function codes as follows.
1) P02 Motor Parameters:
(Rated capacity)
Set the rated capacity of the motor to be used
in kW.
2) P99 Motor Selection:
Select the characteristics of the motor. (Refer
to the descriptions given for P99.)
3) H03 Data Initialization:
Initialize the motor constants. (H03=2)
4) P03 Motor Parameters:
(Rated current):
Set the rated current printed on the nameplate
if the set data differs from the rated current.
- After completion of the initialization, the H03 data returns to 0 (default setting).
- If any value out of the general motor capacity is set to P02, the capacity will be
internally converted to the applicable motor rating (see the table on the next
page).
Содержание Jaguar CUB
Страница 47: ...3 5 Figure 3 2 Alarm Mode Status Transition...
Страница 77: ...5 4...
Страница 78: ...5 5 E codes Extension Terminal Functions...
Страница 80: ...5 7...
Страница 81: ...5 8 C codes Control Functions of Frequency...
Страница 84: ...5 11 y codes Link Functions...
Страница 149: ...8 5 8 3 Common Specifications...
Страница 150: ...8 6...
Страница 153: ...8 9 8 5 External Dimensions 8 5 1 Standard Models...
Страница 154: ...8 10...
Страница 155: ...8 11 8 5 2 Models Available on Order EMC Filter Built in Type...
Страница 156: ...8 12...