xii
Discontinuance
of power-factor
correcting ca-
pacitor
Do not mount power-factor correcting capacitors in the in-
verter primary circuit. (Use the DC reactor to improve the
inverter power factor.) Do not use power-factor correcting
capacitors in the inverter output circuit. An overcurrent trip
will occur, disabling motor operation.
Discontinuance
of surge killer
Do not connect a surge suppressor to the inverter's secon-
dary circuit.
Reducing noise
Use of a filter and shielded wires is typically recommended to
satisfy EMC directives.
Combina-
tion with pe-
ripheral de-
vices
Measures against
surge currents
If an overvoltage trip occurs while the inverter is stopped or
operated under a light load, it is assumed that the surge
current is generated by open/close of the phase-advancing
capacitor in the power system.
* Connect a DC reactor to the inverter.
Megger test
When checking the insulation resistance of the inverter, use a
500 V megger and follow the instructions contained in
Chapter 7, Section 7.4 "Insulation Test."
Control circuit
wiring length
When using remote control, limit the wiring length between
the inverter and operator box to 20 m or less and use twisted
shielded wire.
Wiring length
between inverter
and motor
If long wiring is used between the inverter and the motor, the
inverter will overheat or trip as a result of overcurrent
(high-frequency current flowing into the stray capacitance) in
the wires connected to the phases. Ensure that the wiring is
shorter than 50 m. If this length must be exceeded, lower the
carrier frequency or mount an output circuit filter (OFL).
Wiring size
Select wires with a sufficient capacity by referring to the cur-
rent value or recommended wire size.
Wiring
Wiring type
Do not use one multicore cable in order to connect several
inverters with motors.
Grounding
Securely ground the inverter using the grounding terminal.
Selecting
inverter
capacity
Driving gen-
eral-purpose
motor
Select an inverter according to the applicable motor ratings
listed in the standard specifications table for the inverter.
When high starting torque is required or quick acceleration or
deceleration is required, select an inverter with a capacity
one size greater than the standard.
Transpor-
tation and
storage
Driving special
motors
Select an inverter that meets the following condition:
Inverter rated current > Motor rated current
When transporting or storing inverters, follow the procedures and select locations
that meet the environmental conditions listed in Chapter 1, Section 1.3 "Trans-
portation" and Section 1.4 "Storage Environment."
Содержание Jaguar CUB
Страница 47: ...3 5 Figure 3 2 Alarm Mode Status Transition...
Страница 77: ...5 4...
Страница 78: ...5 5 E codes Extension Terminal Functions...
Страница 80: ...5 7...
Страница 81: ...5 8 C codes Control Functions of Frequency...
Страница 84: ...5 11 y codes Link Functions...
Страница 149: ...8 5 8 3 Common Specifications...
Страница 150: ...8 6...
Страница 153: ...8 9 8 5 External Dimensions 8 5 1 Standard Models...
Страница 154: ...8 10...
Страница 155: ...8 11 8 5 2 Models Available on Order EMC Filter Built in Type...
Страница 156: ...8 12...