Service Menu -> Integration
Menu item
Description
Range
Default
Customised
value
DHW integrat.
enabled
Enables domestic hot water mode of the UI
Yes / No
Yes
Heating integrat.
enabled
Enables the operation of the UI in heating
Yes / No
Yes
DHW waiting time Waiting time to reach the setting set before activation of the integra-
tion in the production of domestic hot water
0 - 240
(5 minute inter-
vals)
20’
Heating waiting time Waiting time to reach the setting set before activation of the integra-
tion in room heating
0 - 240
(5 minute inter-
vals)
20’
Integration mode
Establishes how to integrate the heat generator to the condensing unit,
you can choose between automatic and manual
Auto - Man
Man
Manual activation
temp.
Establishes the outdoor temperature under which central heating
integration is enabled.
-15 ÷ 35 °C
0
Integration band
If the flow temperature of the outdoor unit is lower than the heating-
set value minus the activation band divided by 2, then after a period
equal to the activation delay time, the indoor unit will be turned on.
0 ÷ 15 °C
3
F1 Electricity price Allows to enter the price of electricity in € per kWh for time slot 1
0 ÷ 2,55 €/kWh
0,23
F2 Electricity price Allows to enter the price of electricity in € per kWh for time slot 2
0 ÷ 2,55 €/kWh
0,23
F3 Electricity price Allows to enter the price of electricity in € per kWh for time slot 3
0 ÷ 2,55 €/kWh
0,23
Gas price
Allows to enter the methane price in € per cubic metre.
For other gasses, the value to be inserted must be calculated by
multiplying the user gas price by the correction factor indicated in
the table below:
Gas used
Correction factor
Methane
1
GPL (m
3
)
0,38
GPL (L)
1,45
0 ÷ 2,55 €/m
3
0,95
Service Menu -> Heat Pump
Menu item
Description
Working parameters Sub-menu for working data
Status
Sub-menu for operating state
Maintenance
Sub menu for maintenance operations
Service Menu -> Heat Pump -> Working parameters
Menu item
Description
Flow temperature
Instant outlet temperature from the outdoor unit
Return temperature Outdoor unit return temperature
Calculated plant
setpoint
Flow temperature determined by the outdoor unit
Calculated DHW
setpoint
DHW temperature determined by the outdoor unit
Compr. discharge
temp.
Outdoor unit compressor temperature
Plate exchange temp. Coolant temperature inside the heat exchanger
Evaporator
temperature
Evaporator temperature
External temperature External room temperature
Compressor
frequency
Current compressor frequency
Max compr.
frequency
Indicates the maximum frequency that can be reached by the compressor with the present conditions