1.12 CONTROL PANEL MAIN DIMENSIONS.
1.13 CONTROL PANEL INSTALLATION OPERATIONS.
1) Separate the fixing template from the body of the remote panel
using a screwdriver as a lever in the relative recess (Fig. 13). In-
stall the remote panel away from heat sources and in a suitable
position to detect the room temperature correctly.
2) Install the remote panel using the openings on its rear part
directly onto the wall or on a recess box using the relative sup-
plied screws.
3) Connect the remote panel to the electronic management clamps,
as indicated in the wiring diagram.
The connection is made using wires with a minimum section of
0.50 mm2 and maximum section of 1.5 mm2 and with a maxi-
mum length of 50 metres.
For correct installation, prepare a dedicated line to
connect the control panel according to the Standards
in force regarding electrical systems. If this is not
possible, interference due to other electric cables
could cause malfunctioning of the control panel itself.
4) Fix the body of the remote control to the mount template,
engaging it with pressure.
5) After the Victrix Hybrid devices have been powered, wait about
30 seconds before regulation so that communication between
control panel and the Victrix Hybrid devices has established.
1.14 EXTERNAL TEMPERATURE PROBE.
In the outdoor unit there is an external probe as standard. This
may be used by the control panel to manage temperature control.
Optional external probes may not be connected to the
indoor or outdoor units.