37
Instructions for the installer
ARES TEC ErP: 150 - 200 - 250 - 300 - 350
Type of
Gas
Supply pressure Ø Noz-
zles
Diaphragm
Fan speed
CO
2
levels
Power at ignition
[mbar]
(mm)
[mm]
Min.
Max.
[%]
[%]
FL Min.
FU Max.
Min.
Max.
IG
Nat. gas (G20)
20
7
-
32
100
8,9
8,9
80
Nat. gas (G25)
25
9
-
32
100
8,9
8,9
80
Propane (G31)
37
7
-
31
93
10,8
10,8
80
NOZZLES - PRESSURES - FLOW RATES TABLE