Inspections and maintenance
BMM parameters
Code
Symb.
PARAMETER DESCRIPTION
Unit
Min
Max
Factory settings
803
Srv
Services enabled
0
1
1
48
ChSet
CH#1: Setpoint
°C
30
95
80
784
BC
Local BUS address
0
11
0
816
MI
ModBus Address
1
127
1
817
MT
Timeout Modbus
sec
0
240
30
896
0
Unknown Parameter
0
1
0
799
AC
Input 0/10V
0
2
0
376
DI1
Programmable Input #1
0
3
0
322
Po
Pump Post-circulation
min
1
30
3
341
PL
Pump Minimum Control
%
0
100
30
313
Pr
Pump Maximum Control
%
0
100
100
31
HL
CH#1: Minimum Setpoint
°C
20
105
30
39
HH
CH#1: Maximum Setpoint
°C
20
105
95
792
CHP
CH (Central heating): Maximum Modulation.
%
0
100
100
619
IG
Ignition Modulation
%
32
82
80
645
IDT
Generator: Flame Stabilisation Time
sec
0
30
0
783
Er
Generator: Ignition Attempts
0
10
0
646
0
Unknown Parameter
0
1
0
527
PU
Fan: Pulses/Rev
0
4
2
486
FP
Fan: Proportional gain adjustment
0
50
30
487
FI
Fan: Integral gain adjustment
0
50
9
489
Fpl
Fan: Minimum PWM (pulse width modulation)
%
5
15
8
337
Fr
Modulation gradient
%
1,0
100,0
2,0
526
FU
Fan: Maximum Speed
Hz
50
150
100
319
FH
Maximum Modulation
%
1,0
100,0
100,0 (*93,0)
346
FL
Minimum Modulation
%
1,0
100,0
32,0 (*31,0)
314
Sb
Standby Modulation
%
0
100
26
620
IP
Postpurge: Fan
%
0
100
26
617
IGL
Ignition: Minimum Modulation
%
10
100
32
618
IGH
Maximum Modulation Ignition
%
0
100
82
353
HP
CH PID: Proportional
°K
0
50
25
354
HI
CH PID: Integrative
°K
0
50
12
478
Hd
CH PID: Derivative
°K
0
50
0
34
HY
Burner Hysteresis
°K
5,0
20,0
5,0
336
HS
Temperature Gradient
°C/min
1
30
10
483
rP
Generator: Maximum Differential Temperature
°C
0,0
50,0
30,0
380
AI1
Programmable Sensor #1
0
3
1
777
AFC
APS Control (Burner air flow control)
0
3
0
623
TS
Temperature Sensors
0
1
0
626
TSE
Flue Sensor
0
3
0
805
LV
Mains Voltage
Volt
100
240
230
2590
Burner Power
kW
10
1000
50
(*) = Values for LPG