Appendix
Fieldbus EtherNet/IP
>
General error codes
5682
Revision: 2014-03-05
Error Code
[hex]
Error
Meaning
0x01
NOK
no slave response OR:
master is in the offline mode when requesting the command
0x02
SND
no slave with the old address found
0x03
SD0
slave with address 0 connected
0x04
SD2
slave with the new address already exists
0x05
DE
error when deleting the old address
0x06
error when reading the IO configuration
0x07
SE
error when writing the new address or extended ID code 1
0x08
AT
new address could only be saved temporarily
0x09
ET
extended ID code 1 could only be saved temporarily
0x0A
NA
the slave is not in the LAS
0x0B
ID
parameter or address invalid
0x0C
faulty S-7.4 protocol sequence
0x0D
ST
S-7.4 protocol aborted (timeout)
0x0E
IA
invalid AS-i slave address for the S-7.4 protocol (e.g. B slaves)
0x0F
SSA
AS-i slave has aborted the S-7.4 string
0x10
AS-i S-7.4 no longer connected (no longer in LAS)
0x11
STA
another S-7.4 transfer to the addressed AS-i slave is already active
0x12
HSE
the previous segmented S-7.4 transfer was not yet completed
0x13
IDL
invalid S-7.4 data length
0x14
master is in the wrong operating mode *)
0x16
timeout during command processing
0x17
CMD_PRE
start requirements for S-7.4 command not met:
- wrong slave profile (is not S-7.4) or:
- slave is not in LAS or:
- master is not in the Protected mode
0x18
NM
master is not in the protected mode
0x19
master is not in projection mode
0x20
command could not be processed within the specified time
0xE0...0xEF
CTT2 error detected by AS-i slave;
CTT2 error codes
(
0xF0
invalid CTT2 command
0xF1
invalid CTT2 response
0xF2
S-7.5 data length longer than 30 bytes