9.3 Explanation of the menu
SP1/rP1
Upper / lower limit value for the level at which OUT1 switches�
FH1/FL1
Upper / lower limit for the acceptable range (monitored by OUT1)�
SP2/rP2
Upper / lower limit value for the level at which OUT2 switches�
FH2/FL2
Upper / lower limit for the acceptable range (monitored by OUT2)�
SP3/rP3
Upper / lower limit value for the level at which OUT3 switches�
FH3/FL3
Upper / lower limit for the acceptable range (monitored by OUT3)�
SP4/rP4
Upper / lower limit value for the level at which OUT4 switches�
FH4/FL4
Upper / lower limit for the acceptable range (monitored by OUT4)�
OUx
Output function for OUTx:
Switching signal for the level limit values: hysteresis function [H ��] or window
function [F ��], either normally open [� no] or normally closed [� nc]�
OFS
Offset value for level measurement
EF
Extended functions / opening of menu level 2�
rES
Restore factory setting�
dr1
Switch-off delay for OUT1� The menu item is only active if
OU1 = Hno or Hnc�
dr2
Switch-off delay for OUT2� The menu item is only active if
OU2 = Hno or Hnc�
dr3
Switch-off delay for OUT3� The menu item is only active if
OU3 = Hno or Hnc�
dr4
Switch-off delay for OUT4� The menu item is only active if
OU4 = Hno or Hnc�
FOUx
Response of OUTx in case of a fault�
dFo
Delay time for switching response OUTx in case of a fault�
Uni
Unit of measurement (cm or inch)�
SELd
Type of indication�
LEnG
Length of the rod�
bin
Changing between switching mode and binary mode�