30
11.3 Changing the display unit in the Run mode
(= switching between length indication (cm / inch) and percentage)�
►
Briefly press [Set] in the Run mode�
> The selected unit is displayed for 30 s, the corresponding LED is lit�
With each push of the button the display type is changed�
11.4 Error indications
Possible cause
Recommended measures
[E�000]
Fault in the electronics�
Replace the unit�
[E�031]
Probe detached from the unit; possibly
incorrect setting of the probe length�
Check whether the probe is still
attached to the unit�
Check the parameter [LEnG]�
[E�033]
Measurement disturbed by foam
formation or strong turbulence�
• Install the unit in a still pipe or
bypass�
• Set or increment [dFo]
(→ 10.6.6)
Measurement disturbed by separation
layers (e�g� oil layer on water)�
Remove the oil layer by suction, stir
the medium, verify the composition�
Rod or process connection soiled�
Clean the rod and the process
connection, carry out a reset�*
Installation conditions were not
adhered to�
Observe the notes in "Installation"
(→ 6)
�
Probe length set incorrectly�
Correct the settings
(→ 10.2)
, then
carry out a reset�*
[SCx]
Flashing: short circuit in switching
output x�
Remove the short circuit�
[SC]
Flashing: short circuit in all switching
outputs�
Remove the short circuit�
[PArA]
Faulty data set�
Reset to factory settings
(→ 10.7)
�
** Carry out a reset (power off and on again) after rectifying the fault to reset the error
message�