31
11.5 Output response in different operating states
OUT1��� OUT4
Initialisation
OFF
Normal operation
according to the level and the setting of the output function
(bin, OU1���OU4)
Fault (E�0xx)
OFF for FOUx = OFF;
ON for FOUx = on
12 Technical data and scale drawing
Technical data and scale drawing at www�ifm�com�
12.1 Setting ranges
[LEnG]
cm
inch
Setting range
10���160
4�0���63
Step increment
0�5
0�2
[OFS]
cm
inch
Setting range
0���100
0���39�4
Step increment
0�5
0�2
The setting ranges for the switching limits (SPx, rPx, FHx, FLx) depend on the
probe length (L)� In general the following applies:
cm
inch
min
max
min
max
SPx / FHx
1�5
L - 3
0�6
L - 1�2
rPx / FLx
1�0
L - 3�5
0�4
L - 1�4
Step increment
0�5
0�2
The values apply if [OFS] = 0�
• rPx (FLx) is always smaller than SPx (FHx)� If the value for SPx (FHx) is reduced to a value
≤ rPx (FLx), the position of rPx (FLx) also shifts.
• If rPx (FLx) and SPx (FHx) are close together (approx� 3 x step increment), rPX (FLx) is
changed automatically when SPx (FHx) is increased�
• If there is a greater distance between rPx (FLx) and SPx (FHx), rPx (FLx) maintains the set
value even if SPx (FHx) is increased�