35
• If the level is below SP1, the output is switched� If the level is above SP1 or if
there is a wire break, output 1 switches OFF (alarm message "overflow / wire
break")�
• If the level reaches SP2, output 2 switches (upper preset value reached; finish
refilling)�
• If the level is below SP3, output 3 switches (below lower preset value; start
refilling)�
• If the level is below SP4, the output is switched� If the level is below SP4 or if
there is a wire break, output 4 switches OFF (alarm message "below min� value
/ wire break")�
14.3 Pumping station
Empty the tank / overflow protection with 3 switching outputs�
Replaces 3 float switches�
Configuration of the switching outputs 1 ��� 3 (bin = OFF)
SP1
Maximum value exceeded → alarm.
OU1
Hysteresis function, normally closed (Hnc)�
SP2
Upper value exceeded → submersible pump ON.
OU2
Hysteresis function, normally open (Hno)�
SP3
Lower value reached → submersible pump OFF.
OU3
Hysteresis function, normally closed (Hnc)�
rP1���
rP3
Each slightly below SPx to suppress wave movements (= factory setting)�