NOTICE TO PREVENT TROUBLE AND MALFUNCTION
iTDC
p.5
Also, connecting polarity oppositely may damage the product, so it should be
connected as directed.
The diode is contained in the product packing box.
3
NOTICE FOR INSTALLATION OF DOOR LOCK OR
AUTOMATIC DOOR (24V)
If you control 24V door lock or automatic door, you have to use extra power and
external relay.
Not using extra power and external relay may damage the relay of device and cause
malfunctions.
4
NOTICE FOR CONNECTION OF POWER OR READER
When you supply power to each product,
you must connect power GND to earth
GND.
SMPS (Switching Mode Power Supply) is recommended for power supply
and
IDTECK’s ID40WA is recommended.
If
device and external reader do not use same power, to match the electric
potential, connect each GND to earth GND.
Connecting to earth GND removes potential difference between devices and
prevents malfunctions caused by surge or thunderbolt. Not connecting Earth GND
may cause communication error and malfunction such as changed system
configurations by incoming external noise and shorten the life of the product
5
NOTICE FOR CONNECTION OF COMMUNICATION
Содержание iTDC
Страница 1: ...USER MANUAL iTDC 2 4 DOOR ACCESS CONTROL SYSTEM ...
Страница 20: ...FEATURES iTDC p 13 3 DIMENSION Unit inch mm ...
Страница 22: ...FEATURES iTDC p 15 Internal TCP IP Module IIM100 ...
Страница 37: ...PRODUCT INSTALLATION 6 p 30 1 DESCRIPTION OF PORTS FOR WIRING 1 1 ITDC ITDC SR MAIN BOARD PORT ...
Страница 79: ...p 72 SETTING CHANGES iTDC ...
Страница 87: ...p 80 SETTING CHANGES iTDC ...
Страница 101: ...p 94 SETTING CHANGES iTDC 3 SETTING MENU F3 ...
Страница 112: ...SETTING CHANGES iTDC p 105 ARM CODE PROCESS DETAILS ARM CODE has to be different from DISARM CODE ...
Страница 113: ...p 106 SETTING CHANGES iTDC DISARM CODE PROCESS DETAILS ARM CODE has to be different with DISARM CODE ...
Страница 117: ...p 110 SETTING CHANGES iTDC ...
Страница 135: ...p 128 APPENDIX iTDC But two functions 1 2 cannot be used at the same time ...