12.2 Alarm and Error Message System Behavior
The following table gives an example of these messages and when you can expect them to be displayed.
Message
Displayed When:
Error Clearing/Pump Response
FATAL ERRORS
: The pump and controller will not run while one of these error conditions exists. The Red LED will
blink and the error message will flash on the screen. Users can access the menu system by pressing the MENU key. The red
LED and the message will cease when the error condition has been corrected.
A n a l o g I n p u t # 1
O u t o f R a n g e
The analog input is less than
2.4 mA or greater than 24
mA
Self-Clearing- Pump motor will stop and remain stopped until
the signal is between 2.4 and 24mA. The pump will resume
speed or flow when the signal is returned.
F L O W M E T E R
S I G . L O W / M I S S I N G
The flow meter feedback
signal (Closed Loop
Operation) has fallen below
2.5 ma or is missing.
Self-Clearing – Pump motor will stop, closed loop operation
will cease. Once signal is returned closed loop flow operation
will continue.
- - A L A R M - -
L O W L E V E L
The tank level monitoring
digital input has triggered
Self-Clearing – Pump motor will stop when a tank level input is
activated. When the tank level input is deactivated, the pump
motor will start automatically in remote mode. Manual mode
requires a pump restart (on/off pressed)
- - A L A R M - -
L E A K D E T E C T E D
The leak detection
monitoring digital input has
triggered.
Self Clearing/Self-Latching – Pump motor will stop when the
leak detection input is activated. When the leak input is
deactivated, the pump motor will not start and will require a
manual restart.
P U M P F L O W
N O T D E T E C T E D
The flow detection
monitoring digital input has
triggered. (Only available in
open loop mode)
Not Self-Clearing (Latched) – Pump motor will stop. Pump
may not be restarted until cleared. Pump must return to manual
mode in order to be restarted. (Remote restarts on flow not
detected not allowed)
- - A L A R M - -
A C D R I V E F A U L T
Internal fault
Not Self-Clearing (Latched) - Pump Motor will stop. Record
AC drive error code on AC drive LED screen and Consult
Factory. Cycle power to attempt to clear fault.
A C D R I V E F A U L T
C O M M U N I C A T I O N
Communication error exists
between the MPC VECTOR
controller and the AC
DRIVE
Self-Clearing – Pump motor will stop after 10 seconds of loss of
communications between the controller and AC drive. When
communications are restored the pump will restart.
C O M M U N I C A T I O N
- - E R R O R - -
Communication error exists
between the MPC VECTOR
controller and the
keypad/display module
Not Self-Clearing (Latched) – In Manual Mode the pump will
stop after a 20 second interval if communication is not restored.
In Remote Mode the pump will continue to run when
communications is lost between the keypad and controller.
- - A L A R M - -
P U L S A G U A R D
Flow has fallen below or not
gone above user defined low
flow threshold for 20
seconds.
Not-Self Clearing – Pump motor will stop, closed loop
operation will cease. In manual (local) mode the pump must be
restarted with the on/off key. In remote mode the pump will
keep attempting to restart after each PulsaGuard alarm is
recognized.
Содержание Pulsafeeder MPC Vector
Страница 6: ......
Страница 14: ...8 Figure 1 3 Closed Loop Control Feedback Block Diagram Figure 1 4 Closed Loop Flow Calibration Curve...
Страница 43: ...37 This page is intentionally left blank...
Страница 73: ...67 Continues next page...
Страница 80: ...74 16 Menu Maps...
Страница 81: ...75...
Страница 82: ...76...
Страница 83: ...77...
Страница 84: ...78...
Страница 85: ...79...
Страница 86: ...80...
Страница 87: ...81...
Страница 88: ...82...
Страница 89: ...83...
Страница 90: ...84...
Страница 91: ...85...
Страница 92: ...86...
Страница 93: ...87...
Страница 94: ...88...
Страница 95: ...89...
Страница 96: ...90...
Страница 97: ...91...
Страница 105: ...99 Figure 8 Handheld Remote...
Страница 112: ......
Страница 113: ......
Страница 114: ...and Keypad Functionality BULLETIN No IOM MPCVector UMPC 11 201010 Rv A...