24:
AS
‐
I
NTERFACE
M
ASTER
C
OMMUNICATION
FC5A
M
ICRO
S
MART
U
SER
’
S
M
ANUAL
FC9Y
‐
B1273
24
‐
35
Slave
Address
Shading
Colors
Operating
status
of
the
slave
can
be
confirmed
by
viewing
the
shading
color
at
the
slave
address
on
the
Configure
AS
‐
Interface
Master
dialog
box.
The
screen
display
can
be
updated
by
clicking
the
Refresh
button.
Change
Slave
Address
When
a
slave
is
connected
to
the
AS
‐
Interface
master
module,
the
slave
address
can
be
changed
using
WindLDR
.
To
change
a
slave
address,
from
the
WindLDR
menu
bar,
select
Online
>
Configure
Master
.
The
Configure
AS
‐
Interface
Master
dialog
box
appears.
Click
a
slave
address
to
open
the
Change
Slave
Address
dialog
box.
Select
Slave
A
or
Slave
B,
enter
a
required
address
in
the
New
Address
field,
and
click
OK
.
The
Change
Slave
Address
dialog
box
is
closed.
The
new
slave
address
is
stored
in
the
slave
module
nonvolatile
memory.
If
the
command
is
not
processed
correctly,
the
error
message
“AS
‐
Interface
Master
Error”
and
an
error
code
will
appear.
See
38.
The
address
cannot
be
changed
in
the
following
cases.
Address
Shading
Description
LAS
List
of
active
slaves
LDS
List
of
detected
slaves
LPF
List
of
peripheral
fault
slaves
LPS
List
of
projected
slaves
No
Shade
The
slave
is
not
recognized
by
the
master.
OFF
OFF
OFF
ON/OFF
Blue
Shade
The
slave
is
active.
ON
ON
OFF
ON
Yellow
Shade
The
slave
is
recognized
but
not
enabled
to
operate.
OFF
ON
OFF
OFF
Red
Shade
An
error
was
found
in
the
slave.
ON/OFF
ON/OFF
ON
ON/OFF
Duplicate
slave
addresses
Each
slave
must
have
a
unique
address.
Do
not
connect
two
or
more
slaves
with
the
same
address,
otherwise
the
AS
‐
Interface
master
module
cannot
locate
the
slave
correctly.
When
two
slaves
have
the
same
address
and
different
identification
codes
(ID,
I/O,
ID2,
ID1),
the
AS
‐
Interface
master
mod
‐
ule
detects
an
error.
When
two
slaves
have
the
same
address
and
same
identification
codes,
the
AS
‐
Interface
master
module
cannot
detect
an
error.
Failure
to
observe
this
warning
may
cause
severe
personal
injury
or
heavy
damage
to
property.
When
a
slave
with
address
0
is
connected
to
the
AS
‐
Interface
master
module,
power
up
the
MicroSmart
CPU
module
first.
Approximately
5
seconds
later,
turn
on
the
AS
‐
Interface
power
sup
‐
ply.
If
the
CPU
module
and
AS
‐
Interface
power
supply
are
turned
on
at
the
same
time,
the
AS
‐
Inter
‐
face
master
module
enters
normal
protected
offline.
In
this
mode,
slave
addresses
can
be
changed,
but
the
slave
status
cannot
be
confirmed
on
WindLDR
.
Error
Code
Description
1
An
error
was
found
on
the
expansion
I/O
bus.
7
The
AS
‐
Interface
master
module
is
in
local
mode.
8
The
slave
you
are
trying
to
change
does
not
exist.
A
slave
of
the
designated
new
address
already
exists.
While
a
standard
slave
was
set
at
A
address,
attempt
was
made
to
set
an
A/B
slave
at
B
address
of
the
same
number.
While
an
A/B
slave
was
set
at
B
address,
attempt
was
made
to
set
a
standard
slave
at
A
address
of
the
same
number.
Warning
Caution
Содержание MICROSmart FC5A Series
Страница 1: ...FC5A SERIES FC9Y B1273 1 User s Manual Advanced Volume ...
Страница 2: ......
Страница 8: ...Preface 6 FC5A MicroSmart User s Manual FC9Y B1273 ...
Страница 14: ...TABLE OF CONTENTS vi FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 52: ...4 DATA COMPARISON INSTRUCTIONS 4 10 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 72: ...5 Binary Arithmetic Instructions 5 20 FC5A MicroSmart User s Manual FC9Y B1273 ...
Страница 88: ...7 SHIFT ROTATE INSTRUCTIONS 7 12 FC5A MicroSmart User s Manual FC9Y B1273 ...
Страница 112: ...8 DATA CONVERSION INSTRUCTIONS 8 24 FC5A MicroSmart User s Manual FC9Y B1273 ...
Страница 138: ...11 PROGRAM BRANCHING INSTRUCTIONS 11 14 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 178: ...13 PULSE INSTRUCTIONS 13 32 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 202: ...14 PID INSTRUCTION 14 24 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 206: ...15 DUAL TEACHING TIMER INSTRUCTIONS 15 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 214: ...16 INTELLIGENT MODULE ACCESS INSTRUCTIONS 16 8 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 248: ...21 COMPUTER LINK COMMUNICATION 21 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 272: ...23 MODBUS TCP COMMUNICATION 23 10 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 332: ...25 EXPANSION RS232C RS485 COMMUNICATION 25 16 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 341: ...NOTE FC5A MICROSMART USER S MANUAL FC9Y B1273 1 ...
Страница 342: ...NOTE 2 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...