![IDEC MICROSmart FC5A Series Скачать руководство пользователя страница 246](http://html.mh-extra.com/html/idec/microsmart-fc5a-series/microsmart-fc5a-series_user-manual_617369246.webp)
21:
C
OMPUTER
L
INK
C
OMMUNICATION
21
‐
2
FC5A
M
ICRO
S
MART
U
SER
’
S
M
ANUAL
FC9Y
‐
B1273
Programming
WindLDR
In
the
1:1
computer
link
system,
a
computer
can
be
connected
to
either
port
1
or
2
on
the
MicroSmart
CPU
module.
In
the
1:N
computer
link
system,
a
computer
must
be
connected
to
port
2
on
the
CPU
module
and
every
CPU
module
must
have
a
unique
network
number
0
through
31.
The
Communication
page
in
the
Function
Area
Settings
must
be
pro
‐
grammed
for
each
station
in
the
computer
link
system.
If
required,
communication
parameters
can
also
be
changed.
Since
these
settings
relate
to
the
user
program,
the
user
program
must
be
downloaded
to
the
MicroSmart
after
changing
any
of
these
settings.
1.
From
the
WindLDR
menu
bar,
select
Configuration
>
Comm.
Ports
.
The
Function
Area
Settings
dialog
box
for
Communication
Ports
appears.
2.
In
the
Communication
Mode
pull
‐
down
list
for
Port
1
or
2,
select
Maintenance
Protocol
.
3.
Click
the
Configure
button.
The
Communication
Parameters
dialog
box
appears.
Change
settings,
if
required.
4.
Click
the
OK
button.
Baud
Rate
(bps)
1200,
2400,
4800,
9600,
19200,
38400,
57600,
115200
Data
Bits
7
or
8
Parity
Even,
Odd,
None
Stop
Bits
1
or
2
Receive
Timeout
(ms)
10
to
2540
(10
‐
ms
increments)
(Receive
timeout
is
disabled
when
2550
is
selected.)
Network
Number
0
to
31
Mode
Selection
Input
Any
input
number
Note:
When
a
mode
selection
input
has
been
designated
and
the
mode
selection
input
is
turned
on,
the
selected
communica
‐
tion
parameters
are
enabled.
When
communication
parameters
are
changed
without
designating
a
mode
selection
input,
the
changed
communication
parameters
take
effect
immediately
when
the
user
program
is
downloaded.
Содержание MICROSmart FC5A Series
Страница 1: ...FC5A SERIES FC9Y B1273 1 User s Manual Advanced Volume ...
Страница 2: ......
Страница 8: ...Preface 6 FC5A MicroSmart User s Manual FC9Y B1273 ...
Страница 14: ...TABLE OF CONTENTS vi FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 52: ...4 DATA COMPARISON INSTRUCTIONS 4 10 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 72: ...5 Binary Arithmetic Instructions 5 20 FC5A MicroSmart User s Manual FC9Y B1273 ...
Страница 88: ...7 SHIFT ROTATE INSTRUCTIONS 7 12 FC5A MicroSmart User s Manual FC9Y B1273 ...
Страница 112: ...8 DATA CONVERSION INSTRUCTIONS 8 24 FC5A MicroSmart User s Manual FC9Y B1273 ...
Страница 138: ...11 PROGRAM BRANCHING INSTRUCTIONS 11 14 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 178: ...13 PULSE INSTRUCTIONS 13 32 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 202: ...14 PID INSTRUCTION 14 24 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 206: ...15 DUAL TEACHING TIMER INSTRUCTIONS 15 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 214: ...16 INTELLIGENT MODULE ACCESS INSTRUCTIONS 16 8 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 248: ...21 COMPUTER LINK COMMUNICATION 21 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 272: ...23 MODBUS TCP COMMUNICATION 23 10 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 332: ...25 EXPANSION RS232C RS485 COMMUNICATION 25 16 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 341: ...NOTE FC5A MICROSMART USER S MANUAL FC9Y B1273 1 ...
Страница 342: ...NOTE 2 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...