INsTALLATION
vogue combination boiler -
Installation and Servicing
38 MENU OpERATION
OUTsIDE sENsOR sLOpE
This feature is only accessible if an Outside Sensor has
been fitted to the boiler. Boiler performance can be adjusted
relative to the insulation level of the building. To change the
slope press ENTER and the following screen will be displayed
MENU
Vent System
Switch Pre-Heat
Maximum Flow Temperature
Outside Sensor Slope
Exit
Enter
Press “-” until the following screen is displayed.
MENU
Maximum Flow Temperature
Outside Sensor Slope
Fault Help
Fault History
Exit
Enter
Press ENTER and the following screen will be displayed.
-15°C
20°C
80°C
30°C
Out’
Flow
1.6
Outside Sensor Slope
Exit
Enter
Press “+” and “-“ until the desired setting is displayed.
Press ENTER followed by ExIT to return to normal operation.
FAULT hELp
This feature provides a list of potential corrective actions at an
installer level for all faults detectable by the boiler electronics
Press ENTER and the following screen will be displayed
MENU
Vent System
Switch Pre-Heat
Maximum Flow Temperature
Outside Sensor Slope
Exit
Enter
Press “-” until the following screen is displayed.
MENU
Outside Sensor Slope
Fault Help
Fault History
State of Inputs
Exit
Enter
Press ENTER and the following screen will be displayed.
Overheat Lockout
Fill System to 1.0 Bar
Vent System, Refill System
Check Pump Spins Freely
Check 240V to Pump
Exit
Press “+” and “-“ to scroll through the information.
Press ExIT twice to return to normal operation.
FAULT hIsTOR y
To view the Fault History of the boiler press ENTER and the
following screen will be displayed
MENU
Vent System
Switch Pre-Heat
Maximum Flow Temperature
Outside Sensor Slope
Exit
Enter
Press “-“ until the following screen is displayed.
MENU
Fault Help
Fault History
State of Inputs
State of Outputs
Exit
Enter
Press ENTER and a screen similar to the following will be displayed.
Fault History
Water Pressure: 17 Minutes
Ago
Ignition Lockout: 3 Days Ago
Overheat Lockout: 2 Months
Ago
No Water Flow: 1 Year Ago
Exit
Press “+” and “-“ to view the full list.
Press ExIT twice to return to normal operation.
sTATE OF INpUTs
To view the current Water Pressure, Switched Live Status,
DHW Flow Rate, DHW Temperature, Flow Temperature,
Return Temperature, Flame Status, Outside Temperature,
DHW Switched Live Status and OpenTherm Status press
ENTER and the following screen will be displayed.
MENU
Vent System
Switch Pre-Heat
Maximum Flow Temperature
Outside Sensor Slope
Exit
Enter
Press “-“ until the following screen is displayed.
MENU
Fault History
State of Inputs
State of Outputs
Service Mode Minimum Rate
Exit
Enter
Press ENTER and a screen similar to following will be displayed.
State of Inputs
Water Pressure:
CH Switched Live:
Hot Water Flow Rate:
Hot Water
Temperature:
1.3 Bar
On
5.0 l/min
60°C
Exit
Press “+” and “-“ to view the full list.
Press ExIT twice to return to normal operation.