vogue combination boiler -
Installation and Servicing
INsTALLATION
37 MENU OpERATION
IN
s
T
ALLA
TION
VENT sysTEM
The Vent System feature aids removal of air from the heat
exchanger. The pump will be switched on for 50s and then off
for 10s while the diverter valve is moved between DHW and
CH every 30s. The feature lasts for 5 minutes.
Press ENTER and the following screen will be displayed
MENU
Vent System
Switch Pre-Heat
Maximum Flow Temperature
Outside Sensor Slope
Exit
Enter
Press “+” and the following screen will be displayed.
MENU
Vent System
Switch Pre-heat On/Off
Maximum Flow Temperature
Exit
Enter
Press ENTER and the following screen will be displayed.
Vent System
Pump will be pulsed
On 60s, Off 10s
Diverter Valve
alternates CH/DHW
OFF
Exit
Enter
Press ENTER and the following screen will be displayed.
Vent System
Pump pulsed
On 60s, Off 10s
Diverter Valve
alternates CH/DHW
ON
Exit
The feature will end automatically after 5 minutes, to end
manually press ExIT.
pRE-hEAT
If pre-heat is switched on then the boiler will periodically fire the
burner thereby reducing the time taken to provide hot water.
If pre-heat is switched off the response time will be reduced
although gas consumption will also be reduced.
Press ENTER and the following screen will be displayed
MENU
Vent System
Switch Pre-Heat
Maximum Flow Temperature
Outside Sensor Slope
Exit
Enter
Press ENTER and a screen similar to the following will be
displayed.
Switch Pre-Heat
OFF press
SAVE press
ON
Exit
Enter
To switch Pre-heat off press “-“
To switch Pre-heat on press “+”
To return to normal operation press ExIT twice.
MAxIMUM FLOW TEMpERATURE
It is possible to limit the maximum flow temperature that can
be set from the CH Flow Temperature knob using this feature.
Note that this could prevent adequate room temperature being
achieved in winter.
Press ENTER and the following screen will be displayed.
MENU
Vent System
Switch Pre-Heat
Maximum Flow Temperature
Outside Sensor Slope
Exit
Enter
Press “-“ until the following screen is displayed.
MENU
Switch Pre-Heat
Maximum Flow Temperature
Outside Sensor Slope
Fault Help
Exit
Enter
Press ENTER and a screen similar to following will be
displayed.
Set Maximum Flow Temperature
°C
70
Exit
Enter
Press “+” and “-“ until the desired temperature is displayed and
then ENTER followed by ExIT to return to normal operation.