AHP60 14/18 kW -
Installation, Use and Maintenance
CAUTION:
When choosing the size of the pipes, make sure that the maximum pressure
drop of the system as stated in the technical data in paragraph 2.4.1 is not
exceeded (see useful head).
Always connect the pipes to the connections using the wrench-to-wrench
system.
Make a suitable drain for the safety valve.
It is the installer’s responsibility to check that the expansion vessel is suitable
for the actual capacity of the system.
CAUTION:
A metal filter must be fitted (with a mesh size not exceeding 1000 microns) as
well as a T connector on the return pipe of the system labelled WATER INLET. If
the flow rate switch is tampered with or modified, or if the metal filter and filter-
settler are not fitted to the system, the warranty is immediately void. The filter
and filter-decanter must be kept clean, so please always ensure they are clean
after installation of the appliance and check them periodically.
All units are fitted with a flow rate controller (factory-fitted). If the flow rate
controller is modified or removed, or if the water filter and filter-settler are not
fitted on the unit, the warranty is immediately void. Refer to the wiring diagram
supplied with the appliance for the connection of the flow rate controller. Never
shunt the flow rate controller connections in the terminal block.
The heating system connected to this unit must be installed in compliance with
the standard EN-12828.
3.5.3. Manometric head available
The circulation pump is built into the heat pump. The hydraulic pressure available at the outlet of
the outdoor unit is shown in the graph below.
Figure 9 -
Hydraulic pressures and flow rates available
Water flow