2.6. Operating principle
2.6.1. Production of DHW (winter mode)
When the heat pump is operating, other than in the start-up and transition phases, the inlet
temperature must not fall below 25°C. A lower value may cause system anomalies, including
damage to the compressor. Similarly, the outlet temperature must not exceed 60°C. With
temperatures higher than those indicated, especially if combined with low water flow rates, there
may be anomalies in the operation of the unit, or in the most critical cases, the safety devices
may be tripped.
2.6.2. Operating ranges
This heat pump is designed to operate over an outdoor air temperature range of -20°C to +40°C.
The outlet water temperature depends on the outside air temperature, within the limits provided
in the diagram below
Range of water supply temperatures depending on the ambient temperature
:
Figure 3 - Outlet water temperature that the heat pump may provide according to ambient air temperature
W
ater
T°
[°C]
Evaporator inlet air
temperature [°C]