3.3.4.  Condensate evacuation system 

All the units have been designed so that the base of 

the unit acts as a condensate drainage tray. A plastic 

connector is supplied and is to be installed under the 

base, to connect a hose to channel the condensation 

water.
Each unit is therefore equipped with a hole on the base 

of the hydronic kit on the battery side for the drainage 

of any condensation that may penetrate through the 

pipes of the hydraulic system. As these pipes are well 

insulated, the production of condensation is minimised 

and it is therefore not necessary to connect a drainage 

pipe to this connection.
MORE ESPECIALLY IN THE COLDEST REGIONS, WE 

RECOMMEND INSTALLING SUPPORTS TO RAISE 

THE UNIT TO PREVENT ICE FROM FORMING UNDER 

TDHE UNIT AND DAMAGING IT.

Hole in the 

bottom panel of 

the outdoor unit

Seal

Seal

Drain connector

Figure 8 - Condensate evacuation

3.4.  Installing the control unit

The  Ecomod  Heat  Pump  Control  is  supplied  separately  from  the  heat  pump,  with  a  specific 

installation guide inside its packaging. Refer to this guide to connect this unit.

3.5.  Hydraulic connections

3.5.1.  Accessories to be connected to the external unit 

 -In the same way, the hydraulic connections must comply with good engineering practices 

according to the regulations in force.

 -Before making the hydraulic connections, the supply pipes must be cleaned to avoid contami-

nating the tank with metal or other types of particles.

 -The Plumbing British standard must be respected.

 -Check when hot that the pressure does not exceed the service pressure.

 

-

Recommendations

: for regions where the water is hard, the use of a water softener does not 

imply any change in our Guarantee, provided that the softener is adjusted in line with trade 

standards, and is checked and maintained regularly.

 

-

The water hardness must be greater than 8°f and less than 15.1°f.

3.5.2.  General

 

The hydraulic connections must comply with the national or local regulations; the 

pipes  may  be  made  or  steel  or  galvanised  steel.  Flexible  hoses  may  be  used  if  their 

diameter  is  larger.  The  dimensions  of  the  pipes  must  be  chosen  carefully  to  suit  the 

nominal water flow rate of the appliance and the pressure drops in the hydraulic circuit. 

All of the hydraulic connections must be insulated with closed-cell insulation of adequate 

thickness. The unit must be connected to the pipes with new flexible hoses, not ones 

that  have  already  been  used.  We  recommend  fitting  the  following  components  in  the 

hydraulic circuit:

•   Thermometer with sensor for the reading the temperature in the circuit.
•  Manual valves to isolate the cooler from the hydraulic circuit.
•  Y-shaped  metal  filter  and  filter-settler  (installed  on  the  system  return  pipe)  with  a 

metal mesh not larger than 1mm.

•  Loading unit and discharge valve if required

Содержание ECOMOD AHP60 14 kW

Страница 1: ...rm to the safety and performance speci cation that we require Do not use reconditioned or copy parts that have not been clearly authorised by Ideal For the very latest copy of literature for speci cat...

Страница 2: ......

Страница 3: ...ns 37 4 PRE REQUISITES BEFORE COMMISSIONING 42 4 1 Verification before switching on 42 4 2 Switching On 43 4 3 Commissioning 43 4 4 Adjustment of the heat pump hydraulic flow 43 4 5 Operating diagram...

Страница 4: ...ODUCT LIFE 68 Symbols used in this document INFORMATION This symbol draws attention to comments CAUTION Failure to comply with these instructions may cause damage to the installation or to other objec...

Страница 5: ...accordance with the prevailing regulations and code of practice in particular The legislation on the handling of refrigerants Current I E E BS7671 Wiring Regulations CAUTION This device must be mainta...

Страница 6: ...and work on the machine The elements indicated below are not exhaustive given the diversity of the possible installations and interventions they cannot be considered as an undertaking as to the respo...

Страница 7: ...ene measures Do not smoke PHYSICAL AND CHEMICAL PROPERTIES Colour Colourless Smell Ethereal Hardly perceptible in low concentrations Boiling point 51 7 C at atm press Flash point 648 C Lower flammabil...

Страница 8: ...igerants which may only be carried out by specialised technicians or qualified personnel and return it to the supplier Precautions related to the installation of the refrigerant If local construction...

Страница 9: ...not frost free we recommend that this situation be temporary so as not to alter the system s performance permanently Do not forget to flush the system once the room is frost free If glycol water is us...

Страница 10: ...ry side The electrical connections will only be made when all of the other assembly operations attachment assembly have been carried out Never use a socket for the power supply CAUTION The contract wi...

Страница 11: ...01 07 2022 11 70 Example of recommended connection diagram non exhaustive COMMAND VIA ELECT CABINET TO EXPANSION SYSTEM...

Страница 12: ...technician must receive the appropriate training and instruction for their tasks in safe conditions Operators should be familiar with personal protective equipment and accident prevention rules prescr...

Страница 13: ...see Refrigerant Material Safety Data Sheet You should know that refrigerants may not develop an odor For any intervention on the heat pump system Wear appropriate PPE especially gloves and goggles En...

Страница 14: ...14 70 00U07352240 A_ EN AHP60 14 18 kW Installation Use and Maintenance...

Страница 15: ...values communicated in chap ter 2 4 1 2 3 Definitions Change to monobloc heat pump to be installed outdoors only for heating and or domestic hot water application air water The outdoor air is the ene...

Страница 16: ...h 2 40 3 10 Useful head 1 kPa 61 33 Energy efficiency Water 35 C 55 C Class A A A A Compressor Type Twin Rotary DC Inverter Twin Rotary DC Inverter Oil type ESTER OIL VG74 ESTER OIL VG74 Number of com...

Страница 17: ...ice kg 136 141 The above performances are given for the following operating conditions as per the standard 14511 2018 1 Heating external air temperature 7 dry C temperature Ts 6 C humid temperature Th...

Страница 18: ...of the regulation UE 813 2013 dry temperature humid temperature of the external air 7 C 6 C in out water temperature 47 55 C The tolerance on the value of the total acoustic power level is 2 dB A The...

Страница 19: ...e outside air 7 C 6 C water temperature inlet outlet 47 55 C The tolerance on the value of the total sound power level is of 2dB A Value is determined according to EN 12102 1 2017 used in conjunction...

Страница 20: ...HP60 14 18 kW Installation Use and Maintenance 2 5 Description 2 5 1 Models AHP60 14 18 kW Figure 1 Frame sizes in mm for both 14kW and 18kW Front view RH side view LH side view Top view IN OUT 1 M G...

Страница 21: ...from the front plate then push the panel downwards to free the interlocking tabs view A pull the panel forwards to release it 3 Remove screw number 12 and those on the battery side of the appliance T...

Страница 22: ...indicated especially if combined with low water flow rates there may be anomalies in the operation of the unit or in the most critical cases the safety devices may be tripped 2 6 2 Operating ranges T...

Страница 23: ...flow rate controller Note the water flow rate controller is used to avoid the failure of the anti freeze sensor due to insufficient flow rate but does not guarantee the minimum flow rate required for...

Страница 24: ...ramps steps or disconnected doors that could affect movement and damage the unit 3 Ensure that the unit is kept vertical while it is being moved 4 Before moving the unit check that the equipment is su...

Страница 25: ...l waste in livestock farms or gas emissions from agricultural machinery A few elements to watch for are also shown in Table on page 27 Determining which corrosive elements are present in the environme...

Страница 26: ...appliance does not disturb neighbours or users noise level draughts caused low temperature of the air blown causing a risk of freezing plants in its path Exterior installation on a roof or in an open...

Страница 27: ...cturers Oxides Nitrogen oxides NOX x x x Sulphur oxides SxOy x x Carbon oxides x x Volatile gases or liquids Sulphurs x x x Hydrogen fluoride x x Ozone x x Nitrous oxide Methane x Volatile Organic Com...

Страница 28: ...o reduce the risks it is advisable to study the vibration transmissions from the machine to the building as well as piping reverberation 3 3 2 1 Principle of reflection of the noise emitted Inner cour...

Страница 29: ...0 500 500 Figure 6 Minimum installation clearances around the outdoor unit A B D C E IMPORTANT Do not clog or cover the ventilation openings on the top cover 3 3 3 Minimum technical clearances By foll...

Страница 30: ...Figure 7 Minimum clearances and types of installation Installation under a shelter or an alcove causes the unit s performances to drop To limit this drop an alcove must have 2 open opposite faces in t...

Страница 31: ...he regulations in force Before making the hydraulic connections the supply pipes must be cleaned to avoid contami nating the tank with metal or other types of particles The Plumbing British standard m...

Страница 32: ...er are not fitted to the system the warranty is immediately void The filter and filter decanter must be kept clean so please always ensure they are clean after installation of the appliance and check...

Страница 33: ...first case it is essential to clean before connecting the new heat pump In the second case fitting a filter on the heat pump return will capture any loose deposits The cleaning performed prior to inst...

Страница 34: ...ecialists which can provide the appropriate treatment based on the characteristics of the installation and a monitoring agreement with a guarantee as to the results In the case of a unit where the wat...

Страница 35: ...in position 0 Add water until the pressure of the hydraulic circuit reaches 2 bar The P vent operates automatically run the pump to readjust the pressure Check that there are no leaks After the Start...

Страница 36: ...ent is delivered closed from the factory It must be opened so that it can evacuate the air 3 5 6 1 Precautions when connecting the water supply Supervise all of the operations for connecting the water...

Страница 37: ...arby may cause suffer electromagnetic disturbances to from the unit Be aware of this risk on the installation site We recommend powering the unit electrically with an adequate line and protections and...

Страница 38: ...ations must be carried out when the heat pump is stopped and after disconnecting the electrical power supply These operations must only be carried out by QUALIFIED PERSONNEL Remove the cover without r...

Страница 39: ...emoved last when the unit is disconnected In the power cable comes loose make sure that the active conductors are powered before the earth wire A proximity switch with adequate breaking capacity must...

Страница 40: ...h 2 5 2 The terminal block must be connected in compliance with the remarks below Figure 12 Terminal block APHP60 14 18 kW CAUTION It is important to separate high voltage cables from very low voltage...

Страница 41: ...se voltage 230 50Hz 5 A resistive 1A inductive X 14 1 X 14 2 Default programmable output of heat pump Attention this is not factory configured set to H85 47 Inverter contact withstands single phase vo...

Страница 42: ...e appliance s rating plate Ensure that the voltage is definitive and within the tolerance limits 5 Before switching on check if all of the cover panels have been fitted and attached with the appropria...

Страница 43: ...ing is required before the planned commissioning date back up generators may be used Ecomod heating system only via the tank back up resistors Ecomod hot water system via the gas boiler and the coil t...

Страница 44: ...44 70 00U07352240 A_ EN AHP60 14 18 kW Installation Use and Maintenance Figure 13 Operating diagram 4 5 Operating diagram 4 5 1 14 18 kW...

Страница 45: ...bottle ST1 Temperature sensor on suction line F Dehydration filter DT1 Compressor outlet temperature sensor SV Pressure socket PSHC 1 1 HP pressure switch automatic reset R1 Housing resistor IN1 Inle...

Страница 46: ...52240 A_ EN AHP60 14 18 kW Installation Use and Maintenance 4 6 HMI Navigation U User S Password protected specialist 195 Only in case of default in progress Only if USB flash drive detected with the...

Страница 47: ...LED ON LED if the compressor is active OFF if the compressor is switched off FLASHING if timer is counting down to start the compressor Not used in this application Frost free resistor LED ON LED if t...

Страница 48: ...B stick is present see software instructions Firmware version Fir Installer Error history Hist Installer Only if there is data in the history Access the PSS menu to enter the maintenance technician pa...

Страница 49: ...S menu to enter the maintenance technician password 195 and to activate access to a higher level Once you have fully exited the menus the password privileges are lost and the password needs to be ente...

Страница 50: ...and repair When the heat pump is at fault it displays OFF and the alarm light is on To see the error code you must use PRG2 twice If an automatic reset fault appears the heat pump restarts at the lat...

Страница 51: ...y it is stopped and the error message E008 is displayed This error needs to be reset manually if the compressor is stopped more than 3 times in an hour Check the fan is operating correctly Check the c...

Страница 52: ...or is attached correctly to the terminals CN2 5 6 E641 Failure of the compressor discharge sensor intervention of the manual reset pressure switch closed 42 8bar open 34bar The DT1 sensor is faulty or...

Страница 53: ...igh pressure sensor failure The HP1 high pressure sensor is defective Check that the HP1 sensor is attached correctly to the terminals CN1 3 4 E801 Inverter board communication error The communication...

Страница 54: ...o coupler OPT1 is defective or not powered Check the fan fuse If the functional diagram connections are all present Check Check if opto coupler OPT1 is powered if there is a 12V voltage between the te...

Страница 55: ...circuit break Check heatsink temperature sensor wiring replace inverter board 8 Communication error between inverter card and main board Incorrect communication cabling communication error Replace the...

Страница 56: ...Causes Solutions E 881 Supply voltage out of bounds 7 protection DC power surge Tension High AC input Poor input wiring of food Check power at source voltage Check power source wiring 6 Protection DC...

Страница 57: ...cases we recommend filling the system using an external tap that has been fitted by the installer 7 2 Filling the outdoor unit with water Refer to paragraph 3 6 4 7 3 Prolonged shutdown The methods f...

Страница 58: ...where it is necessary to desolder the pipes we strongly recommend cutting the pipes and not desoldering them with a torch as the flame may trigger the combustion of any oil present It is forbidden to...

Страница 59: ...on the hydraulic circuit X Clean the finned battery with compressed air X Check if the electrical terminals inside the electrical cabinet and on the compressor termianals are attached correctly X Tigh...

Страница 60: ...out the cleaning treatment every three months Wash preferably with hot water 40 60 C and a pH neutral detergent then rinse thoroughly with cold water 50 L m If the maintenance personnel notices that t...

Страница 61: ...qualified technical personnel Place the appliance in a suitable place where there is no risk of leakage of flammable gas Make the installation area inaccessible to third parties Presence of dust wate...

Страница 62: ...r R32 This refrigerant detector must not generate sparks and must be properly sealed 3 Extinguisher A CO2 or powder extinguisher must be available for the following situations Topping up the refrigera...

Страница 63: ...cause corrosion Exception refrigerant lines must be made of corrosion resistant materials or be sufficiently protected against corrosion 7 Checking the electrical components The following safety check...

Страница 64: ...rk on components suitable for use in flammable atmospheres While we cannot completely rule out exceeding the permissible voltages and currents permanent capacitive or inductive loads must not be conne...

Страница 65: ...circuit for repair or other reasons it should be done according to standard procedures In general special care must be taken with regard to the flammability of the refrigerant The following procedure...

Страница 66: ...f drain equipment We recommend that first of all the refrigerant is recovered Before draining take samples of the oil and refrigerant if the refrigerant needs to be treated The important factor is tha...

Страница 67: ...must contain a safety valve and shut off valves that are firmly attached and in good condition Empty recycling bottles are evacuated and must be cooled down before the suction process if possible The...

Страница 68: ...symbol above must not be put with domestic waste and must be collected separately When the appliance has reached the end of its life cycle and needs to be replaced a number of recommendations must be...

Страница 69: ...s with appropriate technical training obtained through courses recognised by the competent authorities The same precautions described in the previous paragraphs must be followed Special attention must...

Страница 70: ...2 Ideal is a trademark of Ideal Boilers Registered Office Ideal Boilers Ltd PO Box 103 National Avenue Kingston Upon Hull HU5 4JN Tel 01482 492251 Fax 01482 448858 Registration No London 322 137 Ideal...

Отзывы: