AHP60 14/18 kW -
Installation, Use and Maintenance
INFORMATION:
If there is a water leak, the component must be changed, by unscrewing it
with two wrenches, as shown in the picture below.
3.5.6.2.
Automatic air vent
The unit is fitted with an air vent valve which
automatically evacuates the air that accumulates
inside the circuit, avoiding unwanted effects such as
corrosion and premature wear or lower efficiency.
It also has a safety function, as if the condenser
breaks, it allows the refrigerant gas to evacuate to
the outside air and avoid transporting it to internal
terminals.
When the air vent remains in the open position, the
air is evacuated automatically.
CAUTION :
The air vent is delivered closed from the factory. It must be opened so that it can
evacuate the air
3.5.6.1.
Precautions when connecting the water supply
•
Supervise all of the operations for connecting the water supply and filling.
•
Before connecting the water supply and filling the system, disconnect the electrical power
supply to the units.
•
The connection of the water supply and filling of the installation must always be carried out in
controlled pressure conditions (max. 1 bar). Ensure that a pressure reducer and a safety valve
have been fitted on the loading/reintegration line.
•
The water in the supply/filling line must be filtered properly beforehand to remove all impurities
and suspended particles. Ensure that a removable screen filter and filter-settler are installed.
• Periodically check and evacuate the air that accumulates in the system.
• Fit an automatic air vent at the highest point of the system.