Modular Power Series
855-340-004_Rev2.0_Instruction Manual
Page
10
of 81
not connect the loads to the DC Output bus bars until the software has been
configured (see Section 3.2.3 or Section 4.2.2).
Figure 4. The DC Output Bus Bars
If using the LDM outputs, an "Output" (la or − depending on polarity)
and "Return" (labelled RTN) connection are provided for each channel (see
Figure 5 and Figure 6).
Figure 5. The LDM
Figure 6. The LDMP
The LDM provides four remotely controlled and monitored outputs, with front
panel overcurrent protection provided by hydraulic-magnetic circuit
breakers (see Section 2.11 for the installation instructions for the breakers).
The LDM maximum current rating is 80 amps. Each output can accept 30
amps maximum, 25 amps continuous.
Table 8. LDM Output Capacity
System Voltage
LDM Output Capacity
12, 24, or 48 V
Up to 4 x 30 A peak output (25 A cont.)
CAUTION
•
Ensure that the current draw on the LDM outputs does not
exceed the output capacity of the power modules or 80
amps, whichever is less.
•
Leave breakers turned off until the software has been
configured (see Section 3.2.3 or Section 4.2.2).